Power Factor Correction Calculator
A low power factor means your supply carries extra current for the same useful power — and the utility may charge you for it. This calculator works out the capacitor size (kVAR) needed to lift your power factor to the target.
Aim for 0.95 — correcting all the way to 1.0 risks over-correction.
Worked Examples
Example 1 — 50 kW load, pf 0.7 → 0.95: tan(acos 0.7) = 1.020, tan(acos 0.95) = 0.329. kVAR = 50 × (1.020 − 0.329) = 50 × 0.691 = 34.6 kVAR.
Example 2 — 100 kW load, pf 0.8 → 0.95: tan(acos 0.8) = 0.750, tan(acos 0.95) = 0.329. kVAR = 100 × (0.750 − 0.329) = 100 × 0.421 = 42.1 kVAR.
Example 3 — 20 kW load, pf 0.6 → 0.9: tan(acos 0.6) = 1.333, tan(acos 0.9) = 0.484. kVAR = 20 × (1.333 − 0.484) = 20 × 0.849 = 17.0 kVAR.
Frequently Asked Questions
1. What is power factor?
The ratio of real power (kW) to apparent power (kVA). A pf of 0.7 means only 70% of the current is doing useful work — the rest is reactive current shuttling back and forth.
2. Why correct the power factor?
Utilities penalise a low power factor, and it wastes capacity: a 50 kW load at pf 0.7 needs 71.4 kVA of supply, but only 52.6 kVA at pf 0.95. Correction frees up that capacity and cuts cable losses.
3. What size capacitor do I install?
The kVAR from this calculator, rounded to the nearest standard step (e.g. 35 kVAR instead of 34.6). Fit it close to the load or at the main panel.
4. Can I over-correct the power factor?
Yes — pushing pf past 1.0 (leading) can raise the voltage and damage equipment. Aim for 0.95, not 1.0.
5. Does power factor correction save energy?
It cuts losses in your cables and transformer, but it does not change what the load itself consumes. The saving is in demand charges and freed capacity, not in the load's kWh.