Use this wire size calculator to find the smallest copper wire that keeps voltage drop under the NEC 3% limit — enter the load current and the one-way cable distance.

Wire Size Calculator

Check which copper wire size keeps the voltage drop under 3%. Enter the load current and the one-way cable distance — the calculator tests 14, 12 and 10 AWG and recommends the smallest size that passes.




Worked Examples

Example 1 — 20 A, 25 m, 230 V: Loop resistance = 2 × distance × Ω/km ÷ 1,000. 12 AWG: 2 × 25 × 5.21 ÷ 1,000 = 0.2605 Ω. Drop = 20 × 0.2605 = 5.21 V = 5.21 ÷ 230 = 2.3% — passes. 14 AWG: loop R = 0.414 Ω, drop = 8.28 V = 3.6% — fails. 10 AWG: drop = 3.28 V = 1.4% — passes. Recommended: 12 AWG (smallest passing size). At 120 V the same 12 AWG run drops 5.21 V = 4.3% — fails, because the same volts lost are a bigger share of a smaller supply.

Example 2 — 10 A, 40 m, 230 V: 14 AWG: loop R = 2 × 40 × 8.28 ÷ 1,000 = 0.6624 Ω. Drop = 10 × 0.6624 = 6.62 V = 2.9% — passes. So a long 10 A lighting run is fine on 14 AWG. 12 AWG would drop only 4.17 V (1.8%).

Frequently Asked Questions

1. Why is the voltage drop limit 3%?
The NEC recommends no more than 3% drop on a branch circuit (5% total for feeder + branch). Beyond that, motors run hot, lights dim, and appliances underperform.

2. Why is the loop resistance twice the one-way distance?
The current travels out on the live wire and back on the neutral, so the full round trip counts. A 25 m run is 50 m of wire.

3. Why is 120 V stricter than 230 V?
The voltage lost in volts is the same, but it is a bigger percentage of a smaller supply. A 5.21 V drop is 2.3% at 230 V but 4.3% at 120 V — so US 120 V circuits need thicker wire for the same distance.

4. Does a bigger wire also cut power loss?
Yes — loss is I²R, and a thicker wire has lower resistance. In Example 1, 10 AWG loses 20² × 0.164 = 65.6 W, while 14 AWG loses 20² × 0.414 = 165.6 W.

5. What about aluminium wire?
Aluminium has higher resistance than copper (about 60% higher for the same size), so you need a bigger size for the same drop. This calculator is for copper only — check your local code for aluminium sizes.