Use this breaker watts calculator to find how many watts any breaker can handle. Enter your breaker size and voltage — the calculator gives the maximum watts and the safe continuous watts using the NEC 80% rule (continuous loads running 3+ hours must stay under 80% of the breaker rating).
Breaker Watts Calculator
Find the maximum watts and the safe continuous watts for any breaker — NEC 80% rule (continuous load = 3+ hours).
Worked Examples
20 A breaker at 120 V: 20 × 120 = 2,400 W maximum, 1,920 W safe continuous. A 1,500 W space heater + 500 W window AC = 2,000 W: under the ceiling but OVER the 1,920 W continuous limit — expect trips if both run for hours.
Overloaded circuit: 1,500 W space heater + 1,100 W microwave = 2,600 W (21.7 A) — over the 20 A breaker rating entirely.
240 V doubles the watts: the same 20 A breaker at 240 V gives 4,800 W maximum / 3,840 W safe.
Breaker Watts Table
| Breaker | 120 V max / safe | 240 V max / safe | Typical wire |
|---|---|---|---|
| 15 A | 1,800 W / 1,440 W | 3,600 W / 2,880 W | 14 AWG |
| 20 A | 2,400 W / 1,920 W | 4,800 W / 3,840 W | 12 AWG |
| 30 A | 3,600 W / 2,880 W | 7,200 W / 5,760 W | 10 AWG |
Frequently Asked Questions
How many watts can a 20 amp breaker handle?
2,400 W maximum at 120 V, but only 1,920 W safe for continuous loads (NEC 80% rule).
What is the 80% rule for breakers?
Continuous loads (running 3+ hours) must not exceed 80% of the breaker rating — NEC 210.19(A) and 210.20(A).
How many watts on a 15 amp breaker?
1,800 W maximum, 1,440 W safe continuous at 120 V.
Does 240 V double the watts on the same breaker?
Yes — watts = volts × amps, so a 20 A breaker gives 4,800 W at 240 V versus 2,400 W at 120 V.
Why does my breaker keep tripping?
The load exceeds the breaker rating or the continuous limit. Check the load with this calculator, and see our AFCI breaker tripping guide.