Circuit Breaker Size Calculator

Size a circuit breaker from the load current. For a continuous load (running 3 hours or more) the NEC 80% rule says the breaker must be rated at least 125% of the load current — and the wire must match the breaker.



Worked Examples

Example 1 — 16 A continuous load: breaker = 16 × 1.25 = 20 A. Use a 20 A breaker with 12 AWG copper wire.

Example 2 — 12 A continuous load: breaker = 12 × 1.25 = 15 A. Use a 15 A breaker with 14 AWG copper wire.

Example 3 — 24 A continuous load: breaker = 24 × 1.25 = 30 A. Use a 30 A breaker with 10 AWG copper wire.

Frequently Asked Questions

1. Why multiply the load current by 1.25?
Because of the NEC 80% rule: a breaker should only carry 80% of its rating on a continuous load (3+ hours). Turning it around, the breaker must be at least load ÷ 0.8 = load × 1.25.

2. Can I use a bigger breaker than the wire allows?
No — the breaker protects the wire. A 30 A breaker on 14 AWG wire (rated 15 A) lets the wire overheat and is a fire risk. Always match the wire to the breaker, never the other way round.

3. What if the load is not continuous?
Then the breaker can be 100% of the load current — no 1.25 multiplier. A 20 A short-run load can use a 20 A breaker (on 12 AWG wire).

4. What is the difference between a breaker and a fuse?
Both protect against overcurrent, but a breaker can be reset after it trips while a fuse must be replaced. Breakers also trip on short circuits in milliseconds.

5. Why does my breaker keep tripping?
Usually an overload (too much load on the circuit), a short circuit, or a failing breaker. Add up the loads on that circuit — if they exceed 80% of the breaker rating on a continuous load, split the circuit or upgrade the wire and breaker together.