Watts to Amps Calculator

Convert watts to amps. Current is power ÷ voltage — I = P ÷ V. For AC loads with a power factor (motors, compressors) divide by the power factor too. The calculator also suggests a breaker size.




Worked Examples

Example 1 — 1,500 W heater at 120 V: I = P ÷ V = 1,500 ÷ 120 = 12.5 A. A 1,500 W space heater draws 12.5 A — it fits a 20 A circuit, but not a 15 A one for continuous use (12.5 × 1.25 = 15.6 A, so a 20 A breaker).

Example 2 — 2,000 W at 230 V: I = 2,000 ÷ 230 = 8.70 A. A 2,000 W water heater on 230 V draws under 9 A.

Example 3 — 3,000 W motor at 240 V, power factor 0.9: I = 3,000 ÷ (240 × 0.9) = 3,000 ÷ 216 = 13.89 A. The power factor pushes the current up — without it you would wrongly expect only 12.5 A.

Frequently Asked Questions

1. What is the watts to amps formula?
I = P ÷ V for DC and resistive AC loads. For AC loads with a power factor, I = P ÷ (V × pf).

2. How many amps is 2,000 W at 120 V?
2,000 ÷ 120 = 16.67 A. For a continuous load, size the breaker at 16.67 × 1.25 = 20.8 A, so use a 25 A breaker.

3. Why does the power factor change the amps?
Real power (watts) is only part of what the circuit carries — with a power factor below 1, the same watts need more current. A 3,000 W motor at pf 0.9 draws 13.89 A instead of 12.5 A.

4. What size breaker do I need for my load?
Work out the amps, multiply by 1.25 for a continuous load, and pick the next standard breaker size (15, 20, 25, 30, 40, 50 A). The calculator above does this for you.

5. Is 1,500 W too much for a 15 A circuit?
1,500 W at 120 V is 12.5 A — that is fine on a 15 A circuit for short use, but for continuous use the NEC 80% rule allows only 1,440 W on a 15 A circuit, so a 1,500 W heater should run on a 20 A circuit.