Star-Delta Starting Current Calculator

A big motor switched straight on (direct-on-line) can draw 6–7 times its running current. Starting it in star first cuts that starting current to one-third — then the starter switches to delta for normal running.



 

Worked Examples

Example 1 — DOL starting current 90 A: star-delta starting current = 90 ÷ 3 = 30 A. The supply sees only a third of the inrush.

Example 2 — DOL starting current 150 A: star-delta starting current = 150 ÷ 3 = 50 A.

Example 3 — 15 kW, 400 V motor (pf 0.85, efficiency 0.9): running current = 15,000 ÷ (1.732 × 400 × 0.85 × 0.9) = 15,000 ÷ 530.0 = 28.3 A. DOL starting current is about 6× running = 169.8 A. Star-delta starting current = 169.8 ÷ 3 = 56.6 A — only 2× running current instead of 6×.

Frequently Asked Questions

1. Why does star-delta reduce the starting current?
In star, each winding gets 1/√3 (58%) of the line voltage, so the current falls to one-third of what it would be in delta. Once the motor is up to speed, the starter switches to delta.

2. Does the running current change?
No. Once switched to delta, the motor runs at its normal full-load current. Only the starting current is reduced.

3. What happens to the starting torque?
It also drops to one-third. Star-delta is only for loads that start light — fans, pumps, and unloaded conveyors. A loaded crusher or mill would stall.

4. When does the starter switch from star to delta?
After a timer, typically 5–10 seconds, when the motor is near full speed. Switching too early causes a second current surge.

5. Which motors can use star-delta starting?
Motors with all six winding ends brought out to the terminal box, rated to run in delta on your supply voltage. Most 3-phase motors above about 5 HP qualify.