Contactor MCQs — Set 6

10 practice questions on sizing a contactor — work out the motor full-load current and pick the next standard AC-3 rating — with answers and explanations.

Q1. A 5.5 kW, 400 V, three-phase motor (pf 0.8) draws about 9.9 A full load. Which AC-3 contactor rating should be selected?

  • (a) 9 A
  • (b) 12 A
  • (c) 25 A
  • (d) 40 A

Answer: (b) 12 A — the rating must exceed the 9.9 A full-load current, and 12 A is the next standard size above it (9 A is too small).

Q2. An 11 kW, 400 V, three-phase motor (pf 0.85) draws about 18.7 A full load. Which AC-3 contactor rating should be selected?

  • (a) 12 A
  • (b) 18 A
  • (c) 25 A
  • (d) 40 A

Answer: (c) 25 A — full-load current I = 11,000 ÷ (1.732 × 400 × 0.85) = 11,000 ÷ 589 = 18.7 A, so the next standard size above 18.7 A is 25 A (18 A is too small).

Q3. A 3 kW, 400 V, three-phase motor (pf 0.8) draws about 5.4 A full load. Which AC-3 contactor rating should be selected?

  • (a) 9 A
  • (b) 12 A
  • (c) 18 A
  • (d) 25 A

Answer: (a) 9 A — I = 3,000 ÷ (1.732 × 400 × 0.8) = 3,000 ÷ 554 = 5.4 A, and 9 A is the next standard size above 5.4 A.

Q4. A 15 kW, 400 V, three-phase motor (pf 0.85) draws about 25.5 A full load. Which AC-3 contactor rating should be selected?

  • (a) 18 A
  • (b) 25 A
  • (c) 32 A
  • (d) 50 A

Answer: (c) 32 A — I = 15,000 ÷ (1.732 × 400 × 0.85) = 15,000 ÷ 589 = 25.5 A, so the next standard size above 25.5 A is 32 A (25 A is too small).

Q5. A 22 kW, 400 V, three-phase motor (pf 0.85) draws about 37.4 A full load. Which AC-3 contactor rating should be selected?

  • (a) 25 A
  • (b) 32 A
  • (c) 40 A
  • (d) 65 A

Answer: (c) 40 A — I = 22,000 ÷ (1.732 × 400 × 0.85) = 22,000 ÷ 589 = 37.4 A, so the next standard size above 37.4 A is 40 A (32 A is too small).

Q6. An 18.5 kW, 400 V, three-phase motor (pf 0.85) draws about 31.4 A full load. Which AC-3 contactor rating should be selected?

  • (a) 25 A
  • (b) 32 A
  • (c) 40 A
  • (d) 50 A

Answer: (b) 32 A — I = 18,500 ÷ (1.732 × 400 × 0.85) = 18,500 ÷ 589 = 31.4 A, and 32 A is the next standard size just above 31.4 A.

Q7. A 9 kW three-phase heater bank at 400 V draws about 13 A. Which AC-1 contactor rating should be selected?

  • (a) 9 A
  • (b) 12 A
  • (c) 18 A
  • (d) 32 A

Answer: (c) 18 A — heater current I = 9,000 ÷ (1.732 × 400) = 9,000 ÷ 693 = 13 A, and as a resistive AC-1 load the next standard size above 13 A is 18 A.

Q8. A single-phase 1.5 kW, 230 V motor (pf 0.85) draws about 7.7 A full load. Which AC-3 contactor rating should be selected?

  • (a) 9 A
  • (b) 12 A
  • (c) 18 A
  • (d) 25 A

Answer: (a) 9 A — I = 1,500 ÷ (230 × 0.85) = 1,500 ÷ 195.5 = 7.7 A, and 9 A is the next standard size above 7.7 A.

Q9. A 5.5 kW motor has a full-load current of 9.9 A. Its starting current is about 6 times full load. What is the approximate starting current?

  • (a) 10 A
  • (b) 30 A
  • (c) 60 A
  • (d) 120 A

Answer: (c) 60 A — starting current ≈ 6 × 9.9 = 59.4 A, about 60 A. The contactor must withstand this making current even though its continuous rating is only 12 A.

Q10. What is the first step when selecting a contactor for a motor?

  • (a) Choose the coil voltage
  • (b) Calculate the motor full-load current from its kW, voltage and power factor
  • (c) Count the auxiliary contacts
  • (d) Choose the enclosure colour

Answer: (b) Calculate the motor full-load current from its kW, voltage and power factor — the AC-3 rating is then chosen as the next standard size above that current.

Also read: Wire Size Calculator | Cable Sizing MCQs | All MCQ Topics