10 practice questions on cable sizing — load current, voltage drop and choosing the right cable size — with answers and explanations.

Q1. A 5 kW single-phase load at 230 V with a power factor of 0.9 draws what load current?

  • (a) 21.7 A
  • (b) 24.2 A
  • (c) 30.2 A
  • (d) 19.3 A

Answer: (b) 24.2 A — I = P ÷ (V × pf) = 5,000 ÷ (230 × 0.9) = 5,000 ÷ 207 = 24.2 A.

Q2. For the load above, allowing 25% for continuous load, the design current is:

  • (a) 24.2 A
  • (b) 28 A
  • (c) 30.2 A
  • (d) 36 A

Answer: (c) 30.2 A — 24.2 × 1.25 = 30.2 A.

Q3. Which copper cable size covers a 30.2 A load?

  • (a) 1.5 mm²
  • (b) 2.5 mm²
  • (c) 4 mm²
  • (d) 1 mm²

Answer: (c) 4 mm² — 4 mm² copper is rated about 32 A, while 2.5 mm² (about 24 A) is too small.

Q4. A cable has a voltage drop of 4.2 V on a 230 V supply. What is the drop as a percentage?

  • (a) 1.8%
  • (b) 4.2%
  • (c) 0.9%
  • (d) 3.0%

Answer: (a) 1.8% — 4.2 ÷ 230 × 100 = 1.8%, which is inside the usual 3% limit for lighting.

Q5. What is the usual allowed voltage drop for lighting circuits?

  • (a) 10%
  • (b) 5%
  • (c) 3%
  • (d) 1%

Answer: (c) 3% — lighting is usually limited to 3%, other loads to 5%; if the drop is higher, use a bigger cable.

Q6. A 1.5 mm² copper cable is rated about 17 A. What is its typical use?

  • (a) Main incomer
  • (b) Lighting circuits
  • (c) Cooker circuits
  • (d) Sub-main feeds

Answer: (b) Lighting circuits — 1.5 mm² is the standard size for lighting; cookers and sub-mains need much bigger cable.

Q7. A 1,000 W load at 230 V draws what current?

  • (a) 2.3 A
  • (b) 4.35 A
  • (c) 8.7 A
  • (d) 0.23 A

Answer: (b) 4.35 A — I = P ÷ V = 1,000 ÷ 230 = 4.35 A.

Q8. A long cable run has too much voltage drop. What is the correct fix?

  • (a) Use a smaller cable
  • (b) Use a bigger cable
  • (c) Lower the supply voltage
  • (d) Fit a bigger fuse

Answer: (b) Use a bigger cable — a bigger cable has lower resistance, so the voltage drop falls.

Q9. Copper vs aluminium cable of the same size: which carries more current?

  • (a) Aluminium carries more
  • (b) Copper carries more
  • (c) They carry the same
  • (d) Aluminium is heavier, so it carries more

Answer: (b) Copper carries more — copper has lower resistance, so it carries more current for the same size and is easier to terminate.

Q10. A 16 mm² copper cable is rated about 76 A. What is its typical use?

  • (a) Lighting circuits
  • (b) Socket outlets
  • (c) Main incomer
  • (d) Doorbell wiring

Answer: (c) Main incomer — 16 mm² is a main-feed size; lighting uses 1.5 mm² and sockets use 2.5 mm².

Also read: Voltage Drop Calculator | Wiring System MCQs | All MCQ Topics