10 practice questions on cable sizing — load current, voltage drop and choosing the right cable size — with answers and explanations.
Q1. A 5 kW single-phase load at 230 V with a power factor of 0.9 draws what load current?
- (a) 21.7 A
- (b) 24.2 A
- (c) 30.2 A
- (d) 19.3 A
Answer: (b) 24.2 A — I = P ÷ (V × pf) = 5,000 ÷ (230 × 0.9) = 5,000 ÷ 207 = 24.2 A.
Q2. For the load above, allowing 25% for continuous load, the design current is:
- (a) 24.2 A
- (b) 28 A
- (c) 30.2 A
- (d) 36 A
Answer: (c) 30.2 A — 24.2 × 1.25 = 30.2 A.
Q3. Which copper cable size covers a 30.2 A load?
- (a) 1.5 mm²
- (b) 2.5 mm²
- (c) 4 mm²
- (d) 1 mm²
Answer: (c) 4 mm² — 4 mm² copper is rated about 32 A, while 2.5 mm² (about 24 A) is too small.
Q4. A cable has a voltage drop of 4.2 V on a 230 V supply. What is the drop as a percentage?
- (a) 1.8%
- (b) 4.2%
- (c) 0.9%
- (d) 3.0%
Answer: (a) 1.8% — 4.2 ÷ 230 × 100 = 1.8%, which is inside the usual 3% limit for lighting.
Q5. What is the usual allowed voltage drop for lighting circuits?
- (a) 10%
- (b) 5%
- (c) 3%
- (d) 1%
Answer: (c) 3% — lighting is usually limited to 3%, other loads to 5%; if the drop is higher, use a bigger cable.
Q6. A 1.5 mm² copper cable is rated about 17 A. What is its typical use?
- (a) Main incomer
- (b) Lighting circuits
- (c) Cooker circuits
- (d) Sub-main feeds
Answer: (b) Lighting circuits — 1.5 mm² is the standard size for lighting; cookers and sub-mains need much bigger cable.
Q7. A 1,000 W load at 230 V draws what current?
- (a) 2.3 A
- (b) 4.35 A
- (c) 8.7 A
- (d) 0.23 A
Answer: (b) 4.35 A — I = P ÷ V = 1,000 ÷ 230 = 4.35 A.
Q8. A long cable run has too much voltage drop. What is the correct fix?
- (a) Use a smaller cable
- (b) Use a bigger cable
- (c) Lower the supply voltage
- (d) Fit a bigger fuse
Answer: (b) Use a bigger cable — a bigger cable has lower resistance, so the voltage drop falls.
Q9. Copper vs aluminium cable of the same size: which carries more current?
- (a) Aluminium carries more
- (b) Copper carries more
- (c) They carry the same
- (d) Aluminium is heavier, so it carries more
Answer: (b) Copper carries more — copper has lower resistance, so it carries more current for the same size and is easier to terminate.
Q10. A 16 mm² copper cable is rated about 76 A. What is its typical use?
- (a) Lighting circuits
- (b) Socket outlets
- (c) Main incomer
- (d) Doorbell wiring
Answer: (c) Main incomer — 16 mm² is a main-feed size; lighting uses 1.5 mm² and sockets use 2.5 mm².
Also read: Voltage Drop Calculator | Wiring System MCQs | All MCQ Topics