Battery Backup Runtime Calculator

How long will your battery keep the load running? Runtime depends on the battery’s stored energy (amp-hours × volts) and how much of it you can actually use.




Lithium: 100%. Lead-acid: 50% (using more shortens its life).



Worked Examples

Example 1 — 100 Ah, 12 V lithium battery, 200 W load: stored energy = 100 × 12 = 1,200 Wh. Usable = 1,200 × 100% DoD × 85% efficiency = 1,020 Wh. Runtime = 1,020 ÷ 200 = 5.1 hours.

Example 2 — 150 Ah, 24 V battery, 80% DoD, 600 W load: stored = 150 × 24 = 3,600 Wh. Usable = 3,600 × 0.8 × 0.85 = 2,448 Wh. Runtime = 2,448 ÷ 600 = 4.08 hours.

Example 3 — 200 Ah, 12 V lead-acid battery, 50% DoD, 300 W load: stored = 200 × 12 = 2,400 Wh. Usable = 2,400 × 0.5 × 0.9 = 1,080 Wh. Runtime = 1,080 ÷ 300 = 3.6 hours. Lead-acid gives less usable energy because only half the capacity should be used regularly.

Frequently Asked Questions

1. What is depth of discharge (DoD)?
The share of the battery's capacity you actually use. Lithium batteries can use about 100%, lead-acid only about 50% on a regular basis — going deeper shortens a lead-acid battery's life.

2. Why does the inverter reduce my runtime?
Converting DC to AC loses roughly 10–15% as heat. An 85% efficient inverter delivers only 85 Wh of AC for every 100 Wh taken from the battery.

3. How do I make the backup last longer?
Use a bigger battery (more Ah), switch to lithium (higher usable DoD), or cut the load — turning off one 100 W load can add hours.

4. Does a bigger battery always mean longer backup?
Yes — runtime scales directly with usable watt-hours. Double the Ah and you double the runtime at the same load.

5. Can I use the full Ah printed on a lead-acid battery?
Only in an emergency. Regularly draining a lead-acid battery below 50% cuts its life from years to months.