Electrical Troubleshooting MCQs — Set 8
10 practice questions on a motor that will not start — supply, starter, capacitor, overload and winding checks, with answers explained.
Q1. A single-phase motor hums loudly but does not turn. What is the most likely cause?
- (a) The motor is running normally
- (b) The start capacitor has failed, or the motor is mechanically jammed — it has torque to hum but not to start
- (c) The supply voltage is too high
- (d) The motor is overloaded with too little load
Answer: (b) The start capacitor has failed, or the motor is mechanically jammed — it has torque to hum but not to start — a failed start capacitor removes the starting torque, and a seized bearing stops rotation the same way.
Q2. A motor will not start and you measure 0 V at its terminals with the starter switched on. Where is the fault?
- (a) Inside the motor windings
- (b) Upstream — in the supply, starter, contactor or overload device feeding the motor
- (c) In the motor capacitor
- (d) In the motor bearings
Answer: (b) Upstream — in the supply, starter, contactor or overload device feeding the motor — 0 V at the terminals proves power is not reaching the motor at all.
Q3. A motor starts, runs for a minute, then stops and will not restart until it cools down. What is the most likely cause?
- (a) A blown fuse
- (b) The thermal overload has tripped — the motor is overloaded, poorly ventilated, or drawing excess current
- (c) The supply is disconnected
- (d) The capacitor is too large
Answer: (b) The thermal overload has tripped — the motor is overloaded, poorly ventilated, or drawing excess current — thermal overloads reset only after cooling, which matches the symptom exactly.
Q4. You test a motor’s three windings with a multimeter. Two read 5 Ω and one reads OL. What does this mean?
- (a) The motor is healthy
- (b) One winding is open-circuited and the motor needs rewinding or replacement
- (c) The motor is shorted
- (d) The supply is faulty
Answer: (b) One winding is open-circuited and the motor needs rewinding or replacement — all three windings of a healthy motor read similar low resistances; OL on one means that winding is broken.
Q5. A three-phase motor runs but in the wrong direction. What is the correct fix?
- (a) Replace the motor
- (b) Swap any two of the three supply phases at the starter or motor terminals
- (c) Increase the supply voltage
- (d) Fit a larger breaker
Answer: (b) Swap any two of the three supply phases at the starter or motor terminals — swapping two phases reverses the rotating magnetic field and so reverses the motor.
Q6. A motor’s overload relay keeps tripping, and the clamp meter shows the motor drawing 24 A while its nameplate full-load current is 16 A. What is the diagnosis?
- (a) The overload relay is set too high
- (b) The motor is genuinely overloaded or has a developing fault — it is drawing 50% more than its rated current
- (c) The motor is running with no load
- (d) The supply frequency is wrong
Answer: (b) The motor is genuinely overloaded or has a developing fault — it is drawing 50% more than its rated current — 24 A against a 16 A rating is 1.5× full load, so the overload is tripping correctly.
Q7. A single-phase motor will not start and the start capacitor reads OL on the capacitance range. What does this mean?
- (a) The capacitor is healthy
- (b) The capacitor has failed open and must be replaced with one of the same rating
- (c) The motor windings are shorted
- (d) The supply is at the wrong frequency
Answer: (b) The capacitor has failed open and must be replaced with one of the same rating — a good capacitor shows its rated capacitance; OL means it is open and cannot provide starting torque.
Q8. A motor trips its breaker at the instant of starting, but runs fine once started by hand. What should you suspect?
- (a) The motor is underloaded
- (b) Excessive starting current — a jammed load, a wrong starter setting, or a winding fault raising the inrush
- (c) The overload relay is set too high
- (d) The capacitor is too big
Answer: (b) Excessive starting current — a jammed load, a wrong starter setting, or a winding fault raising the inrush — starting current is already several times running current, so any extra load at start-up can trip the breaker.
Q9. A motor winding measures 0.3 MΩ to earth on a megger test. What is the correct action?
- (a) Run the motor — 0.3 MΩ is fine
- (b) Do not run it — the insulation is below the 1 MΩ pass level; dry out or repair the motor and retest first
- (c) Fit a larger fuse
- (d) Swap two phases
Answer: (b) Do not run it — the insulation is below the 1 MΩ pass level; dry out or repair the motor and retest first — 0.3 MΩ means significant leakage to earth, a shock and tripping risk.
Q10. A contactor chatters (buzzes and vibrates) when the motor is switched on, and the motor runs unevenly. What is the most likely cause?
- (a) The motor is too powerful
- (b) Low or unstable voltage at the contactor coil — a loose connection or voltage drop in the control circuit
- (c) The overload relay is set correctly
- (d) The motor bearings are new
Answer: (b) Low or unstable voltage at the contactor coil — a loose connection or voltage drop in the control circuit — a coil that cannot hold firmly chatters, making and breaking the motor supply.