Electrical Troubleshooting MCQs — Set 2

10 practice questions on the half-split technique — dividing a circuit in two to locate a fault in the fewest tests, with answers explained.

Q1. What is the half-split method of fault-finding?

  • (a) Cutting every wire in half
  • (b) Testing at the midpoint of a circuit to decide which half contains the fault, then repeating on that half
  • (c) Replacing half the components at once
  • (d) Splitting the supply voltage in half

Answer: (b) Testing at the midpoint of a circuit to decide which half contains the fault, then repeating on that half — each test eliminates half the circuit, so the fault is found in very few steps.

Q2. A lighting circuit has 8 lamps in a row and all are dead. You test at lamp 4 and find 230 V present. Where is the fault?

  • (a) Between the supply and lamp 4
  • (b) Between lamp 4 and lamp 8, or in lamps 5–8 themselves
  • (c) In the main supply to the house
  • (d) In lamp 1 only

Answer: (b) Between lamp 4 and lamp 8, or in lamps 5–8 themselves — voltage reaching the midpoint proves the first half is healthy, so the fault lies in the second half.

Q3. In the same 8-lamp circuit, you test at lamp 4 and find 0 V. What do you do next?

  • (a) Replace all 8 lamps
  • (b) Test at lamp 2 — the midpoint of the faulty first half
  • (c) Test at lamp 8
  • (d) Increase the breaker rating

Answer: (b) Test at lamp 2 — the midpoint of the faulty first half — the fault is in the first half, so you split that half again.

Q4. Why is half-splitting faster than testing every point in order from the supply?

  • (a) It uses a better multimeter
  • (b) Each test rules out half of the remaining circuit instead of one point at a time
  • (c) It skips the need for safety checks
  • (d) It repairs the fault automatically

Answer: (b) Each test rules out half of the remaining circuit instead of one point at a time — an 8-point circuit can be narrowed to one point in about 3 tests instead of up to 8.

Q5. You test continuity along a cable from the supply end. At the quarter point the reading is about 0 Ω, but at the midpoint it reads OL (open). Where is the break?

  • (a) Between the supply and the quarter point
  • (b) Between the quarter point and the midpoint
  • (c) Beyond the midpoint
  • (d) There is no break at all

Answer: (b) Between the quarter point and the midpoint — continuity is good up to the quarter point and lost by the midpoint, so the open lies in that section.

Q6. When should you use half-splitting instead of checking every connection?

  • (a) Only when the circuit has many points in series, such as a long run of lights or sockets
  • (b) Only on single-socket circuits
  • (c) Only when the breaker is off
  • (d) Never — it is always slower

Answer: (a) Only when the circuit has many points in series, such as a long run of lights or sockets — with only two or three points, testing each one in order is just as fast.

Q7. A cable run has 4 junction boxes in series (A, B, C, D) and the far end is dead. Testing at box B shows 230 V. Testing at box C shows 0 V. Where is the fault?

  • (a) Between the supply and box A
  • (b) Between box B and box C
  • (c) Between box C and box D
  • (d) After box D

Answer: (b) Between box B and box C — voltage is present at B but lost by C, so the break or bad joint is in that section.

Q8. What is the main risk of half-splitting on a live circuit?

  • (a) It takes too long
  • (b) Working on live conductors at the test points — live testing must follow safe procedures and proper test equipment
  • (c) The multimeter battery runs out
  • (d) The circuit becomes a ring

Answer: (b) Working on live conductors at the test points — live testing must follow safe procedures and proper test equipment — half-splitting often means live voltage checks, so isolation, proving the tester, and PPE matter.

Q9. A string of 16 sockets is dead at the far end only — the first 12 work. Where should your first half-split test be?

  • (a) At socket 1
  • (b) At socket 12, the last working socket, to confirm where supply is lost
  • (c) At socket 16
  • (d) At the meter

Answer: (b) At socket 12, the last working socket, to confirm where supply is lost — the boundary between working and dead is the most informative test point; then split the dead section (13–16) further.

Q10. After half-splitting narrows a fault to one cable section, what confirms the exact fault?

  • (a) Guessing which joint looks oldest
  • (b) A continuity or insulation test on that isolated section, with the supply off
  • (c) Turning the power back on and watching for sparks
  • (d) Replacing the whole circuit

Answer: (b) A continuity or insulation test on that isolated section, with the supply off — dead testing on the isolated section proves whether it is open, shorted, or has low insulation.

Also read: Power Loss Formula | All MCQ Topics