Electrical Troubleshooting MCQs — Set 2
10 practice questions on the half-split technique — dividing a circuit in two to locate a fault in the fewest tests, with answers explained.
Q1. What is the half-split method of fault-finding?
- (a) Cutting every wire in half
- (b) Testing at the midpoint of a circuit to decide which half contains the fault, then repeating on that half
- (c) Replacing half the components at once
- (d) Splitting the supply voltage in half
Answer: (b) Testing at the midpoint of a circuit to decide which half contains the fault, then repeating on that half — each test eliminates half the circuit, so the fault is found in very few steps.
Q2. A lighting circuit has 8 lamps in a row and all are dead. You test at lamp 4 and find 230 V present. Where is the fault?
- (a) Between the supply and lamp 4
- (b) Between lamp 4 and lamp 8, or in lamps 5–8 themselves
- (c) In the main supply to the house
- (d) In lamp 1 only
Answer: (b) Between lamp 4 and lamp 8, or in lamps 5–8 themselves — voltage reaching the midpoint proves the first half is healthy, so the fault lies in the second half.
Q3. In the same 8-lamp circuit, you test at lamp 4 and find 0 V. What do you do next?
- (a) Replace all 8 lamps
- (b) Test at lamp 2 — the midpoint of the faulty first half
- (c) Test at lamp 8
- (d) Increase the breaker rating
Answer: (b) Test at lamp 2 — the midpoint of the faulty first half — the fault is in the first half, so you split that half again.
Q4. Why is half-splitting faster than testing every point in order from the supply?
- (a) It uses a better multimeter
- (b) Each test rules out half of the remaining circuit instead of one point at a time
- (c) It skips the need for safety checks
- (d) It repairs the fault automatically
Answer: (b) Each test rules out half of the remaining circuit instead of one point at a time — an 8-point circuit can be narrowed to one point in about 3 tests instead of up to 8.
Q5. You test continuity along a cable from the supply end. At the quarter point the reading is about 0 Ω, but at the midpoint it reads OL (open). Where is the break?
- (a) Between the supply and the quarter point
- (b) Between the quarter point and the midpoint
- (c) Beyond the midpoint
- (d) There is no break at all
Answer: (b) Between the quarter point and the midpoint — continuity is good up to the quarter point and lost by the midpoint, so the open lies in that section.
Q6. When should you use half-splitting instead of checking every connection?
- (a) Only when the circuit has many points in series, such as a long run of lights or sockets
- (b) Only on single-socket circuits
- (c) Only when the breaker is off
- (d) Never — it is always slower
Answer: (a) Only when the circuit has many points in series, such as a long run of lights or sockets — with only two or three points, testing each one in order is just as fast.
Q7. A cable run has 4 junction boxes in series (A, B, C, D) and the far end is dead. Testing at box B shows 230 V. Testing at box C shows 0 V. Where is the fault?
- (a) Between the supply and box A
- (b) Between box B and box C
- (c) Between box C and box D
- (d) After box D
Answer: (b) Between box B and box C — voltage is present at B but lost by C, so the break or bad joint is in that section.
Q8. What is the main risk of half-splitting on a live circuit?
- (a) It takes too long
- (b) Working on live conductors at the test points — live testing must follow safe procedures and proper test equipment
- (c) The multimeter battery runs out
- (d) The circuit becomes a ring
Answer: (b) Working on live conductors at the test points — live testing must follow safe procedures and proper test equipment — half-splitting often means live voltage checks, so isolation, proving the tester, and PPE matter.
Q9. A string of 16 sockets is dead at the far end only — the first 12 work. Where should your first half-split test be?
- (a) At socket 1
- (b) At socket 12, the last working socket, to confirm where supply is lost
- (c) At socket 16
- (d) At the meter
Answer: (b) At socket 12, the last working socket, to confirm where supply is lost — the boundary between working and dead is the most informative test point; then split the dead section (13–16) further.
Q10. After half-splitting narrows a fault to one cable section, what confirms the exact fault?
- (a) Guessing which joint looks oldest
- (b) A continuity or insulation test on that isolated section, with the supply off
- (c) Turning the power back on and watching for sparks
- (d) Replacing the whole circuit
Answer: (b) A continuity or insulation test on that isolated section, with the supply off — dead testing on the isolated section proves whether it is open, shorted, or has low insulation.
Also read: Power Loss Formula | All MCQ Topics