10 practice questions on transformers — turns ratio, kVA sizing, efficiency and iron vs copper losses — with answers and explanations.

Q1. A transformer has 1,000 turns on the primary (230 V) and 100 turns on the secondary. What is the secondary voltage?

  • (a) 2,300 V
  • (b) 23 V
  • (c) 230 V
  • (d) 2.3 V

Answer: (b) 23 V — voltage ratio = turns ratio, so V2 = 230 × (100 ÷ 1,000) = 23 V.

Q2. In a step-up transformer, the secondary winding has:

  • (a) Fewer turns than the primary
  • (b) More turns than the primary
  • (c) The same number of turns as the primary
  • (d) No turns at all

Answer: (b) More turns than the primary — more secondary turns give a higher secondary voltage.

Q3. A 50 kW load has a power factor of 0.8. What is the apparent power in kVA?

  • (a) 40 kVA
  • (b) 62.5 kVA
  • (c) 50 kVA
  • (d) 80 kVA

Answer: (b) 62.5 kVA — kVA = kW ÷ pf = 50 ÷ 0.8 = 62.5 kVA.

Q4. For the 62.5 kVA load above, you add 25% for future growth. Which standard transformer size do you pick?

  • (a) 75 kVA
  • (b) 100 kVA
  • (c) 50 kVA
  • (d) 150 kVA

Answer: (b) 100 kVA — 62.5 × 1.25 = 78.1 kVA, which is above the 75 kVA standard size, so you go up to 100 kVA.

Q5. The iron (core) losses of a transformer depend mainly on:

  • (a) The load current
  • (b) The supply voltage and frequency
  • (c) The ambient temperature only
  • (d) The load power factor

Answer: (b) The supply voltage and frequency — iron losses are practically constant and do not change with load.

Q6. The copper losses of a transformer vary with:

  • (a) The load current
  • (b) The square of the load current
  • (c) The supply voltage
  • (d) The frequency

Answer: (b) The square of the load current — copper loss = I²R, so doubling the current quadruples the loss.

Q7. Why are transformers rated in kVA and not in kW?

  • (a) Because kVA is always bigger than kW
  • (b) Because the total power a transformer must handle does not depend on the load’s power factor
  • (c) Because transformers have no losses
  • (d) Because kW is only used for motors

Answer: (b) Because the total power a transformer must handle does not depend on the load’s power factor — the transformer supplies both real and reactive power.

Q8. An ideal transformer has 100 V and 10 A on the primary and 200 V on the secondary. What is the secondary current?

  • (a) 20 A
  • (b) 10 A
  • (c) 5 A
  • (d) 2.5 A

Answer: (c) 5 A — power in = power out, so 100 × 10 = 200 × I, giving I = 5 A.

Q9. You need to run a 10 kW load at 0.8 power factor from a generator. What size generator should you choose?

  • (a) 10 kVA
  • (b) 12.5 kVA exactly
  • (c) At least 15 kVA
  • (d) 8 kVA

Answer: (c) At least 15 kVA — the load needs 10 ÷ 0.8 = 12.5 kVA, so you choose the next size up with a margin.

Q10. Transformer oil is used for:

  • (a) Lubrication only
  • (b) Cooling and insulation
  • (c) Increasing the voltage
  • (d) Reducing the number of turns

Answer: (b) Cooling and insulation — the oil carries heat away from the windings and insulates them.

Also read: Power Loss Formula | AC Circuit MCQs | All MCQ Topics