Synchronous Motor MCQs — Set 6
10 practice questions on the synchronous condenser — using an over-excited synchronous motor to correct power factor.
Q1. What is a synchronous condenser?
- (a) A capacitor bank connected to the supply
- (b) An over-excited synchronous motor running at no load
- (c) An induction motor running at no load
- (d) A type of transformer
Answer: (b) An over-excited synchronous motor running at no load — it draws leading current and supplies reactive power to the system.
Q2. What does a synchronous condenser supply to the power system?
- (a) Active power in kW
- (b) Leading reactive power in kVAr
- (c) Direct current
- (d) Mechanical power to a load
Answer: (b) Leading reactive power in kVAr — the leading current cancels the lagging reactive current of inductive loads.
Q3. What is the main advantage of a synchronous condenser over a static capacitor bank?
- (a) It is much cheaper to install
- (b) It gives smooth, stepless control of reactive power by varying the excitation
- (c) It needs no maintenance
- (d) It supplies active power as well
Answer: (b) It gives smooth, stepless control of reactive power by varying the excitation — capacitors switch in fixed steps, while excitation can be adjusted continuously.
Q4. A factory has a lagging power factor because of its induction motors. How can a synchronous motor help?
- (a) By drawing more lagging current
- (b) By running over-excited so it supplies leading reactive power and improves the overall power factor
- (c) By reducing the supply voltage
- (d) By increasing the load on the induction motors
Answer: (b) By running over-excited so it supplies leading reactive power and improves the overall power factor — the leading kVAr offsets the lagging kVAr of the other loads.
Q5. A load draws 50 kW at 0.8 power factor. What is its apparent power?
- (a) 40 kVA
- (b) 62.5 kVA
- (c) 50 kVA
- (d) 100 kVA
Answer: (b) 62.5 kVA — apparent power = kW ÷ pf = 50 ÷ 0.8 = 62.5 kVA.
Q6. A load draws 50 kW at 0.8 power factor (62.5 kVA apparent power). What reactive power does it draw?
- (a) 12.5 kVAr
- (b) 25 kVAr
- (c) 37.5 kVAr
- (d) 50 kVAr
Answer: (c) 37.5 kVAr — kVAr = √(kVA² − kW²) = √(62.5² − 50²) = √1,406.25 = 37.5 kVAr.
Q7. A synchronous condenser can also absorb reactive power when needed. How?
- (a) By running under-excited, so it draws lagging current
- (b) By running over-excited, so it draws lagging current
- (c) By stopping the motor
- (d) By reversing the phase sequence
Answer: (a) By running under-excited, so it draws lagging current — reducing excitation makes it absorb reactive power instead of supplying it.
Q8. An over-excited synchronous motor running at no load has approximately what power factor?
- (a) Unity
- (b) Zero lagging
- (c) Zero leading
- (d) 0.8 lagging
Answer: (c) Zero leading — at no load it draws almost purely leading reactive current, so the power factor is near zero leading.
Q9. Which device is best for power factor correction in a plant where the load varies widely?
- (a) A fixed capacitor bank
- (b) A synchronous condenser, because its reactive output can be varied smoothly with load
- (c) A resistor bank
- (d) An autotransformer
Answer: (b) A synchronous condenser, because its reactive output can be varied smoothly with load — fixed capacitors cannot follow a varying reactive demand.
Q10. A load draws 80 kW at 0.8 power factor. What is its apparent power?
- (a) 64 kVA
- (b) 80 kVA
- (c) 100 kVA
- (d) 120 kVA
Answer: (c) 100 kVA — apparent power = kW ÷ pf = 80 ÷ 0.8 = 100 kVA.
Also read: Separately Excited DC Motor | All MCQ Topics