Synchronous Motor MCQs — Set 6

10 practice questions on the synchronous condenser — using an over-excited synchronous motor to correct power factor.

Q1. What is a synchronous condenser?

  • (a) A capacitor bank connected to the supply
  • (b) An over-excited synchronous motor running at no load
  • (c) An induction motor running at no load
  • (d) A type of transformer

Answer: (b) An over-excited synchronous motor running at no load — it draws leading current and supplies reactive power to the system.

Q2. What does a synchronous condenser supply to the power system?

  • (a) Active power in kW
  • (b) Leading reactive power in kVAr
  • (c) Direct current
  • (d) Mechanical power to a load

Answer: (b) Leading reactive power in kVAr — the leading current cancels the lagging reactive current of inductive loads.

Q3. What is the main advantage of a synchronous condenser over a static capacitor bank?

  • (a) It is much cheaper to install
  • (b) It gives smooth, stepless control of reactive power by varying the excitation
  • (c) It needs no maintenance
  • (d) It supplies active power as well

Answer: (b) It gives smooth, stepless control of reactive power by varying the excitation — capacitors switch in fixed steps, while excitation can be adjusted continuously.

Q4. A factory has a lagging power factor because of its induction motors. How can a synchronous motor help?

  • (a) By drawing more lagging current
  • (b) By running over-excited so it supplies leading reactive power and improves the overall power factor
  • (c) By reducing the supply voltage
  • (d) By increasing the load on the induction motors

Answer: (b) By running over-excited so it supplies leading reactive power and improves the overall power factor — the leading kVAr offsets the lagging kVAr of the other loads.

Q5. A load draws 50 kW at 0.8 power factor. What is its apparent power?

  • (a) 40 kVA
  • (b) 62.5 kVA
  • (c) 50 kVA
  • (d) 100 kVA

Answer: (b) 62.5 kVA — apparent power = kW ÷ pf = 50 ÷ 0.8 = 62.5 kVA.

Q6. A load draws 50 kW at 0.8 power factor (62.5 kVA apparent power). What reactive power does it draw?

  • (a) 12.5 kVAr
  • (b) 25 kVAr
  • (c) 37.5 kVAr
  • (d) 50 kVAr

Answer: (c) 37.5 kVAr — kVAr = √(kVA² − kW²) = √(62.5² − 50²) = √1,406.25 = 37.5 kVAr.

Q7. A synchronous condenser can also absorb reactive power when needed. How?

  • (a) By running under-excited, so it draws lagging current
  • (b) By running over-excited, so it draws lagging current
  • (c) By stopping the motor
  • (d) By reversing the phase sequence

Answer: (a) By running under-excited, so it draws lagging current — reducing excitation makes it absorb reactive power instead of supplying it.

Q8. An over-excited synchronous motor running at no load has approximately what power factor?

  • (a) Unity
  • (b) Zero lagging
  • (c) Zero leading
  • (d) 0.8 lagging

Answer: (c) Zero leading — at no load it draws almost purely leading reactive current, so the power factor is near zero leading.

Q9. Which device is best for power factor correction in a plant where the load varies widely?

  • (a) A fixed capacitor bank
  • (b) A synchronous condenser, because its reactive output can be varied smoothly with load
  • (c) A resistor bank
  • (d) An autotransformer

Answer: (b) A synchronous condenser, because its reactive output can be varied smoothly with load — fixed capacitors cannot follow a varying reactive demand.

Q10. A load draws 80 kW at 0.8 power factor. What is its apparent power?

  • (a) 64 kVA
  • (b) 80 kVA
  • (c) 100 kVA
  • (d) 120 kVA

Answer: (c) 100 kVA — apparent power = kW ÷ pf = 80 ÷ 0.8 = 100 kVA.