Synchronous Motor MCQs — Set 4
10 practice questions on starting a synchronous motor — why it cannot self-start, damper winding, pony motor and VFD methods.
Q1. Why can a synchronous motor not start by itself?
- (a) It has no stator winding
- (b) The stator field rotates too fast for the stationary rotor, with its inertia, to lock on to
- (c) It has no field winding
- (d) It needs a higher supply voltage
Answer: (b) The stator field rotates too fast for the stationary rotor, with its inertia, to lock on to — the rotor cannot follow the rapidly alternating torque, so average starting torque is zero.
Q2. When a synchronous motor is started with its damper winding, how does it start?
- (a) As a DC motor
- (b) As a synchronous motor directly
- (c) As an induction motor
- (d) As a stepper motor
Answer: (c) As an induction motor — the damper bars act like a squirrel cage, producing induction torque until the rotor nears synchronous speed.
Q3. In the pony motor starting method, what does the small auxiliary motor do?
- (a) It supplies the DC excitation
- (b) It brings the synchronous motor rotor close to synchronous speed before synchronising
- (c) It cools the main motor
- (d) It drives the load directly
Answer: (b) It brings the synchronous motor rotor close to synchronous speed before synchronising — the pony motor is usually a small induction motor coupled to the shaft.
Q4. When is the DC excitation switched on during starting?
- (a) At standstill, before the supply is switched on
- (b) When the rotor is running close to synchronous speed
- (c) Only after full load is applied
- (d) Never — it is always on
Answer: (b) When the rotor is running close to synchronous speed — then the rotor poles lock to the stator field and the motor pulls into synchronism.
Q5. How does a variable frequency drive (VFD) start a synchronous motor?
- (a) By increasing the voltage suddenly
- (b) By starting at a very low frequency and ramping it up gradually so the rotor can follow
- (c) By short-circuiting the stator
- (d) By reversing the phase sequence
Answer: (b) By starting at a very low frequency and ramping it up gradually so the rotor can follow — at low frequency the rotating field is slow enough for the rotor to lock on.
Q6. During damper-winding starting, what should be done with the field winding?
- (a) Left open-circuited
- (b) Short-circuited through a suitable resistance
- (c) Connected to the AC supply
- (d) Removed from the rotor
Answer: (b) Short-circuited through a suitable resistance — this prevents dangerously high voltages being induced in the field winding while the rotor is slipping.
Q7. Why must the field winding not be left open-circuited while a synchronous motor is being started?
- (a) The motor would run too fast
- (b) High voltages induced in the open field winding can damage its insulation
- (c) The stator would overheat
- (d) The damper winding would melt
Answer: (b) High voltages induced in the open field winding can damage its insulation — the rotating stator field cuts the stationary field winding at slip frequency, inducing a large voltage.
Q8. Which starting method is most commonly used for large synchronous motors?
- (a) Pony motor starting
- (b) Damper (amortisseur) winding starting
- (c) Direct-on-line starting without any aid
- (d) Star-delta starting
Answer: (b) Damper (amortisseur) winding starting — it is simple, rugged and built into the rotor, so most large synchronous motors use it.
Q9. What is the starting torque of a synchronous motor started as an induction motor through its damper winding?
- (a) Very high, several times full-load torque
- (b) Low to moderate, usually enough for light loads
- (c) Zero
- (d) Equal to pull-out torque
Answer: (b) Low to moderate, usually enough for light loads — damper-winding starting torque is limited, so heavy loads are started unloaded or with reduced load.
Q10. After the motor has pulled into synchronism, what current flows in the damper winding?
- (a) Full-load current
- (b) Starting current
- (c) Practically no current, because there is no relative motion between rotor and stator field
- (d) The DC excitation current
Answer: (c) Practically no current, because there is no relative motion between rotor and stator field — at synchronous speed the damper bars cut no flux, so no current is induced.