Synchronous Motor MCQs — Set 4

10 practice questions on starting a synchronous motor — why it cannot self-start, damper winding, pony motor and VFD methods.

Q1. Why can a synchronous motor not start by itself?

  • (a) It has no stator winding
  • (b) The stator field rotates too fast for the stationary rotor, with its inertia, to lock on to
  • (c) It has no field winding
  • (d) It needs a higher supply voltage

Answer: (b) The stator field rotates too fast for the stationary rotor, with its inertia, to lock on to — the rotor cannot follow the rapidly alternating torque, so average starting torque is zero.

Q2. When a synchronous motor is started with its damper winding, how does it start?

  • (a) As a DC motor
  • (b) As a synchronous motor directly
  • (c) As an induction motor
  • (d) As a stepper motor

Answer: (c) As an induction motor — the damper bars act like a squirrel cage, producing induction torque until the rotor nears synchronous speed.

Q3. In the pony motor starting method, what does the small auxiliary motor do?

  • (a) It supplies the DC excitation
  • (b) It brings the synchronous motor rotor close to synchronous speed before synchronising
  • (c) It cools the main motor
  • (d) It drives the load directly

Answer: (b) It brings the synchronous motor rotor close to synchronous speed before synchronising — the pony motor is usually a small induction motor coupled to the shaft.

Q4. When is the DC excitation switched on during starting?

  • (a) At standstill, before the supply is switched on
  • (b) When the rotor is running close to synchronous speed
  • (c) Only after full load is applied
  • (d) Never — it is always on

Answer: (b) When the rotor is running close to synchronous speed — then the rotor poles lock to the stator field and the motor pulls into synchronism.

Q5. How does a variable frequency drive (VFD) start a synchronous motor?

  • (a) By increasing the voltage suddenly
  • (b) By starting at a very low frequency and ramping it up gradually so the rotor can follow
  • (c) By short-circuiting the stator
  • (d) By reversing the phase sequence

Answer: (b) By starting at a very low frequency and ramping it up gradually so the rotor can follow — at low frequency the rotating field is slow enough for the rotor to lock on.

Q6. During damper-winding starting, what should be done with the field winding?

  • (a) Left open-circuited
  • (b) Short-circuited through a suitable resistance
  • (c) Connected to the AC supply
  • (d) Removed from the rotor

Answer: (b) Short-circuited through a suitable resistance — this prevents dangerously high voltages being induced in the field winding while the rotor is slipping.

Q7. Why must the field winding not be left open-circuited while a synchronous motor is being started?

  • (a) The motor would run too fast
  • (b) High voltages induced in the open field winding can damage its insulation
  • (c) The stator would overheat
  • (d) The damper winding would melt

Answer: (b) High voltages induced in the open field winding can damage its insulation — the rotating stator field cuts the stationary field winding at slip frequency, inducing a large voltage.

Q8. Which starting method is most commonly used for large synchronous motors?

  • (a) Pony motor starting
  • (b) Damper (amortisseur) winding starting
  • (c) Direct-on-line starting without any aid
  • (d) Star-delta starting

Answer: (b) Damper (amortisseur) winding starting — it is simple, rugged and built into the rotor, so most large synchronous motors use it.

Q9. What is the starting torque of a synchronous motor started as an induction motor through its damper winding?

  • (a) Very high, several times full-load torque
  • (b) Low to moderate, usually enough for light loads
  • (c) Zero
  • (d) Equal to pull-out torque

Answer: (b) Low to moderate, usually enough for light loads — damper-winding starting torque is limited, so heavy loads are started unloaded or with reduced load.

Q10. After the motor has pulled into synchronism, what current flows in the damper winding?

  • (a) Full-load current
  • (b) Starting current
  • (c) Practically no current, because there is no relative motion between rotor and stator field
  • (d) The DC excitation current

Answer: (c) Practically no current, because there is no relative motion between rotor and stator field — at synchronous speed the damper bars cut no flux, so no current is induced.

Also read: Separately Excited DC Motor | All MCQ Topics