Switchgear MCQs — Set 5

10 practice questions comparing arc interruption media — air, oil, vacuum and SF6 — their strengths, uses and drawbacks, with answers and explanations.

Q1. Which arc-quenching medium has the highest dielectric strength?

  • (a) Air
  • (b) Oil
  • (c) Vacuum
  • (d) SF6 gas

Answer: (d) SF6 gas — SF6 has several times the dielectric strength of air at the same pressure, which is why it is used in compact high-voltage gear.

Q2. SF6 gas used in switchgear is:

  • (a) Flammable and toxic
  • (b) Colourless, odourless, non-flammable and electronegative
  • (c) A liquid at room temperature
  • (d) Corrosive to copper

Answer: (b) Colourless, odourless, non-flammable and electronegative — its electronegative nature lets it capture free electrons and quench the arc quickly.

Q3. In a vacuum circuit breaker, the arc is extinguished because:

  • (a) Oil cools the contacts
  • (b) The vacuum gives very fast dielectric recovery after current zero
  • (c) Compressed air blows it out
  • (d) SF6 absorbs the arc

Answer: (b) The vacuum gives very fast dielectric recovery after current zero — with almost no gas molecules present, the gap regains its insulating strength almost instantly.

Q4. In a minimum-oil circuit breaker, oil is used:

  • (a) Only for arc extinction, not for insulating the whole tank
  • (b) To fill the entire tank like a bulk-oil breaker
  • (c) To lubricate the mechanism
  • (d) To cool the busbars

Answer: (a) Only for arc extinction, not for insulating the whole tank — that is the difference from a bulk-oil breaker, which needs a large volume of oil.

Q5. What is the main drawback of air as an arc-quenching medium?

  • (a) It is expensive
  • (b) It needs large clearances because of its low dielectric strength
  • (c) It is flammable
  • (d) It cannot be used above 1 kV

Answer: (b) It needs large clearances because of its low dielectric strength — air-insulated switchgear is therefore bulky compared with SF6 or vacuum gear.

Q6. Which medium is used in gas-insulated switchgear (GIS)?

  • (a) Air
  • (b) Oil
  • (c) SF6
  • (d) Nitrogen only

Answer: (c) SF6 — GIS encloses the conductors and breakers in earthed metal housings filled with pressurised SF6 gas.

Q7. What is a major environmental concern with SF6?

  • (a) It is a very potent greenhouse gas
  • (b) It is radioactive
  • (c) It is flammable
  • (d) It dissolves in rain

Answer: (a) It is a very potent greenhouse gas — SF6 has a global warming potential about 23,500 times that of CO2, so leaks must be prevented and gas must be recovered.

Q8. A major disadvantage of bulk-oil circuit breakers is:

  • (a) Carbonisation of the oil after repeated operations, needing frequent oil changes
  • (b) They are too small for outdoor use
  • (c) They cannot break AC current
  • (d) They need a vacuum pump

Answer: (a) Carbonisation of the oil after repeated operations, needing frequent oil changes — each arc leaves carbon in the oil, lowering its dielectric strength.

Q9. Which arc-quenching medium is best suited to very frequent switching, such as capacitor-bank switching?

  • (a) Bulk oil
  • (b) Air
  • (c) Vacuum
  • (d) Minimum oil

Answer: (c) Vacuum — vacuum interrupters handle thousands of operations with very little contact wear, ideal for frequent switching duty.

Q10. In an SF6 puffer-type breaker, the arc is quenched by:

  • (a) A blast of SF6 gas forced across the arc at contact separation
  • (b) Oil spray
  • (c) A vacuum chamber
  • (d) Compressed nitrogen

Answer: (a) A blast of SF6 gas forced across the arc at contact separation — the moving piston compresses SF6 and puffs it through a nozzle over the arc.

Also read: Breaker Watts Calculator | All MCQ Topics