Switchgear MCQs — Set 5
10 practice questions comparing arc interruption media — air, oil, vacuum and SF6 — their strengths, uses and drawbacks, with answers and explanations.
Q1. Which arc-quenching medium has the highest dielectric strength?
- (a) Air
- (b) Oil
- (c) Vacuum
- (d) SF6 gas
Answer: (d) SF6 gas — SF6 has several times the dielectric strength of air at the same pressure, which is why it is used in compact high-voltage gear.
Q2. SF6 gas used in switchgear is:
- (a) Flammable and toxic
- (b) Colourless, odourless, non-flammable and electronegative
- (c) A liquid at room temperature
- (d) Corrosive to copper
Answer: (b) Colourless, odourless, non-flammable and electronegative — its electronegative nature lets it capture free electrons and quench the arc quickly.
Q3. In a vacuum circuit breaker, the arc is extinguished because:
- (a) Oil cools the contacts
- (b) The vacuum gives very fast dielectric recovery after current zero
- (c) Compressed air blows it out
- (d) SF6 absorbs the arc
Answer: (b) The vacuum gives very fast dielectric recovery after current zero — with almost no gas molecules present, the gap regains its insulating strength almost instantly.
Q4. In a minimum-oil circuit breaker, oil is used:
- (a) Only for arc extinction, not for insulating the whole tank
- (b) To fill the entire tank like a bulk-oil breaker
- (c) To lubricate the mechanism
- (d) To cool the busbars
Answer: (a) Only for arc extinction, not for insulating the whole tank — that is the difference from a bulk-oil breaker, which needs a large volume of oil.
Q5. What is the main drawback of air as an arc-quenching medium?
- (a) It is expensive
- (b) It needs large clearances because of its low dielectric strength
- (c) It is flammable
- (d) It cannot be used above 1 kV
Answer: (b) It needs large clearances because of its low dielectric strength — air-insulated switchgear is therefore bulky compared with SF6 or vacuum gear.
Q6. Which medium is used in gas-insulated switchgear (GIS)?
- (a) Air
- (b) Oil
- (c) SF6
- (d) Nitrogen only
Answer: (c) SF6 — GIS encloses the conductors and breakers in earthed metal housings filled with pressurised SF6 gas.
Q7. What is a major environmental concern with SF6?
- (a) It is a very potent greenhouse gas
- (b) It is radioactive
- (c) It is flammable
- (d) It dissolves in rain
Answer: (a) It is a very potent greenhouse gas — SF6 has a global warming potential about 23,500 times that of CO2, so leaks must be prevented and gas must be recovered.
Q8. A major disadvantage of bulk-oil circuit breakers is:
- (a) Carbonisation of the oil after repeated operations, needing frequent oil changes
- (b) They are too small for outdoor use
- (c) They cannot break AC current
- (d) They need a vacuum pump
Answer: (a) Carbonisation of the oil after repeated operations, needing frequent oil changes — each arc leaves carbon in the oil, lowering its dielectric strength.
Q9. Which arc-quenching medium is best suited to very frequent switching, such as capacitor-bank switching?
- (a) Bulk oil
- (b) Air
- (c) Vacuum
- (d) Minimum oil
Answer: (c) Vacuum — vacuum interrupters handle thousands of operations with very little contact wear, ideal for frequent switching duty.
Q10. In an SF6 puffer-type breaker, the arc is quenched by:
- (a) A blast of SF6 gas forced across the arc at contact separation
- (b) Oil spray
- (c) A vacuum chamber
- (d) Compressed nitrogen
Answer: (a) A blast of SF6 gas forced across the arc at contact separation — the moving piston compresses SF6 and puffs it through a nozzle over the arc.
Also read: Breaker Watts Calculator | All MCQ Topics