Single-Phase Motor MCQs — Set 9
10 practice questions on testing and maintaining single-phase motors — capacitors, windings, insulation and rotation — with answers and explanations.
Q1. How is a suspected faulty starting capacitor most reliably checked?
- (a) By measuring its capacitance with a capacitance meter and comparing it with its marked value
- (b) By shaking it and listening for a rattle
- (c) By measuring its weight
- (d) By connecting it directly across the mains
Answer: (a) By measuring its capacitance with a capacitance meter and comparing it with its marked value — a capacitor that has lost much of its capacitance, or reads open or shorted, must be replaced.
Q2. When testing a single-phase motor’s windings with a multimeter, what does a very low resistance between a winding terminal and the motor frame indicate?
- (a) A healthy winding
- (b) An earth fault — the winding insulation has failed
- (c) A faulty capacitor
- (d) A worn bearing
Answer: (b) An earth fault — the winding insulation has failed — winding-to-frame resistance should be very high (megohms); a low reading means the winding is touching the frame.
Q3. Which winding of a split-phase motor normally has the higher resistance?
- (a) The main winding
- (b) The auxiliary (starting) winding
- (c) Both have exactly equal resistance
- (d) The rotor winding
Answer: (b) The auxiliary (starting) winding — it is wound with thinner wire and has more turns, giving the higher resistance that creates the starting phase split.
Q4. What instrument is used to measure the insulation resistance of a motor winding?
- (a) A clamp meter
- (b) A megger (insulation resistance tester)
- (c) A tachometer
- (d) A wattmeter
Answer: (b) A megger (insulation resistance tester) — it applies a high DC test voltage (typically 500 V) and measures the leakage resistance in megohms.
Q5. Before working on a single-phase motor, what is the first safety step?
- (a) Run the motor for 10 minutes to warm it up
- (b) Isolate the supply and prove it dead, and discharge the capacitor before touching terminals
- (c) Remove the fan cover only
- (d) Increase the fuse rating
Answer: (b) Isolate the supply and prove it dead, and discharge the capacitor before touching terminals — a charged capacitor can hold a dangerous voltage after the supply is switched off.
Q6. How is the direction of rotation of a PSC ceiling-fan motor reversed?
- (a) By reversing the supply live and neutral
- (b) By swapping the capacitor from one side of the auxiliary winding to the other (reversing the auxiliary winding connections)
- (c) By fitting a bigger capacitor
- (d) By turning the fan upside down
Answer: (b) By swapping the capacitor from one side of the auxiliary winding to the other (reversing the auxiliary winding connections) — this reverses the phase sequence of the rotating field.
Q7. A 4-pole single-phase motor runs at 1,440 rpm on 50 Hz. What is its slip in rpm (not percent)?
- (a) 10 rpm
- (b) 30 rpm
- (c) 60 rpm
- (d) 150 rpm
Answer: (c) 60 rpm — synchronous speed is 1,500 rpm, so slip speed = 1,500 − 1,440 = 60 rpm.
Q8. What does a no-load test of a single-phase induction motor mainly reveal?
- (a) The breakdown torque
- (b) The no-load current, iron and friction losses, and whether the motor runs smoothly
- (c) The locked-rotor current
- (d) The capacitor’s voltage rating
Answer: (b) The no-load current, iron and friction losses, and whether the motor runs smoothly — a high no-load current can point to a winding fault or tight bearings.
Q9. Which device protects a single-phase motor against sustained overload?
- (a) A centrifugal switch
- (b) A thermal overload relay (or built-in thermal protector)
- (c) A run capacitor
- (d) A shading coil
Answer: (b) A thermal overload relay (or built-in thermal protector) — it trips when the current stays above the rated value long enough to overheat the windings.
Q10. When a single-phase motor is rewound, why must the replacement capacitor match the original voltage rating or exceed it?
- (a) A lower-rated capacitor would be cheaper
- (b) The capacitor sees more than the supply voltage in the starting circuit, and an underrated one can fail or burst
- (c) The capacitor controls the motor speed
- (d) The voltage rating sets the motor’s pole count
Answer: (b) The capacitor sees more than the supply voltage in the starting circuit, and an underrated one can fail or burst — always replace with the same capacitance and an equal or higher voltage rating.