Sensor MCQs — Set 2

10 practice questions on temperature sensors — Pt100 RTDs, thermocouples, thermistors and how they are wired.

Q1. What is the resistance of a Pt100 RTD at 0 °C?

  • (a) 0 Ω
  • (b) 100 Ω
  • (c) 138.5 Ω
  • (d) 1000 Ω

Answer: (b) 100 Ω — “Pt100” means a platinum resistance sensor that is 100 Ω at 0 °C.

Q2. A Pt100 RTD has a temperature coefficient of 0.385 Ω/°C. What is its resistance at 100 °C?

  • (a) 100 Ω
  • (b) 119.25 Ω
  • (c) 138.5 Ω
  • (d) 200 Ω

Answer: (c) 138.5 Ω — R = 100 + (0.385 × 100) = 100 + 38.5 = 138.5 Ω.

Q3. What is the resistance of a Pt100 RTD at 50 °C?

  • (a) 150 Ω
  • (b) 119.25 Ω
  • (c) 109.6 Ω
  • (d) 100 Ω

Answer: (b) 119.25 Ω — R = 100 + (0.385 × 50) = 100 + 19.25 = 119.25 Ω.

Q4. What is the resistance of a Pt100 RTD at 25 °C?

  • (a) 125 Ω
  • (b) 100 Ω
  • (c) 109.6 Ω
  • (d) 96.15 Ω

Answer: (c) 109.6 Ω — R = 100 + (0.385 × 25) = 100 + 9.625 = 109.625 Ω, about 109.6 Ω.

Q5. On which effect does a thermocouple work?

  • (a) Hall effect
  • (b) Seebeck effect — a voltage is produced at the junction of two different metals when it is heated
  • (c) Piezoelectric effect
  • (d) Photoelectric effect

Answer: (b) Seebeck effect — a voltage is produced at the junction of two different metals when it is heated — the voltage rises with the temperature difference between the hot and cold junctions.

Q6. What is the usual measuring range of a Type K thermocouple?

  • (a) −40 °C to +750 °C
  • (b) −200 °C to +350 °C
  • (c) −200 °C to +1260 °C
  • (d) 0 °C to +100 °C

Answer: (c) −200 °C to +1260 °C — Type K (chromel–alumel) is the most widely used general-purpose thermocouple and covers the widest range of the common types.

Q7. What is the usual measuring range of a Type J thermocouple?

  • (a) −200 °C to +1260 °C
  • (b) −40 °C to +750 °C
  • (c) −200 °C to +350 °C
  • (d) 0 °C to +1800 °C

Answer: (b) −40 °C to +750 °C — Type J (iron–constantan) is used for moderate temperatures but its iron wire rusts, so it is not used at high temperatures.

Q8. What is the usual measuring range of a Type T thermocouple?

  • (a) −200 °C to +350 °C
  • (b) −40 °C to +750 °C
  • (c) −200 °C to +1260 °C
  • (d) 0 °C to +1000 °C

Answer: (a) −200 °C to +350 °C — Type T (copper–constantan) is accurate at low and cryogenic temperatures.

Q9. How does the resistance of an NTC thermistor change as temperature rises?

  • (a) It rises
  • (b) It falls
  • (c) It stays the same
  • (d) It becomes zero at 100 °C

Answer: (b) It falls — NTC means Negative Temperature Coefficient: more heat frees more charge carriers, so resistance drops sharply.

Q10. Why is a 3-wire connection used with an RTD instead of a 2-wire connection?

  • (a) To increase the RTD resistance
  • (b) To cancel out the error caused by the resistance of the connecting leads
  • (c) To allow the RTD to work on AC supply
  • (d) To double the measuring range

Answer: (b) To cancel out the error caused by the resistance of the connecting leads — the third wire lets the instrument measure and subtract the lead resistance, which matters because the RTD itself changes by only 0.385 Ω per °C.

Also read: Power Loss Formula | All MCQ Topics