Relay MCQs — Set 7
10 practice questions on distance relays — impedance measurement, Zone 1 and Zone 2 settings, and transmission-line protection.
Q1. What quantity does a distance relay measure to decide if there is a fault?
- (a) Only the current
- (b) Only the voltage
- (c) The impedance, from the ratio of voltage to current
- (d) The temperature of the line
Answer: (c) The impedance, from the ratio of voltage to current — impedance is proportional to the distance from the relay to the fault.
Q2. Zone 1 of a distance relay typically covers what percentage of the protected line?
- (a) 20%
- (b) 50%
- (c) 80%
- (d) 150%
Answer: (c) 80% — Zone 1 is set to about 80% of the protected line length and trips instantly.
Q3. Why is Zone 1 set to 80% of the line and not 100%?
- (a) To save on relay cost
- (b) To avoid overreaching into the next line section because of measurement errors in the CTs, VTs and line impedance
- (c) To make the relay slower
- (d) Because the last 20% of the line cannot develop faults
Answer: (b) To avoid overreaching into the next line section because of measurement errors in the CTs, VTs and line impedance — a 100% setting could trip for a fault on the next line.
Q4. What is the usual Zone 2 setting of a distance relay?
- (a) 80% of the line, instantaneous
- (b) About 120% of the line, with a time delay
- (c) 50% of the line, with a time delay
- (d) 200% of the line, instantaneous
Answer: (b) About 120% of the line, with a time delay — Zone 2 covers the whole line plus part of the next section as backup, typically delayed by about 0.3–0.5 seconds.
Q5. How does the operating time of a distance relay change with the distance to the fault?
- (a) A closer fault trips faster, because the measured impedance is lower
- (b) A closer fault trips slower
- (c) The operating time is the same for every fault
- (d) The relay never trips for a close-in fault
Answer: (a) A closer fault trips faster, because the measured impedance is lower — the relay sees a smaller impedance for a fault nearer to it.
Q6. What is a distance relay mainly used to protect?
- (a) Small domestic circuits
- (b) Transmission lines
- (c) Battery chargers
- (d) DC motors only
Answer: (b) Transmission lines — it is the standard protection for high-voltage lines, where fault current alone is not a reliable guide.
Q7. A fault occurs at 90% of the line length from the relay. How does the distance relay respond?
- (a) Zone 1 trips it instantly
- (b) Zone 1 does not reach it, so Zone 2 trips it after its time delay
- (c) The relay does not operate at all
- (d) The relay trips the whole grid instantly
Answer: (b) Zone 1 does not reach it, so Zone 2 trips it after its time delay — Zone 1 covers only the first 80%, so a fault at 90% falls in Zone 2.
Q8. A transmission line is 100 km long. How far does Zone 1 of its distance relay reach?
- (a) 20 km
- (b) 50 km
- (c) 80 km
- (d) 120 km
Answer: (c) 80 km — Zone 1 covers 80% of the line, so 0.8 × 100 = 80 km.
Q9. Why is a distance relay preferred for long transmission lines?
- (a) It needs no CTs or VTs
- (b) Its operating time depends on the distance to the fault, giving selective grading between line sections
- (c) It works without any power supply
- (d) It can measure the line length directly in kilometres
Answer: (b) Its operating time depends on the distance to the fault, giving selective grading between line sections — the relay nearest the fault trips first.
Q10. What happens to the impedance measured by a distance relay when the fault is closer to the relay?
- (a) It increases
- (b) It decreases, because less line impedance lies between the relay and the fault
- (c) It stays the same
- (d) It becomes infinite
Answer: (b) It decreases, because less line impedance lies between the relay and the fault — impedance is proportional to the length of line to the fault.
Also read: Power Loss Formula | All MCQ Topics