Relay MCQs — Set 4
10 practice questions on IDMT overcurrent relays — plug setting, pickup current, plug setting multiplier and the time multiplier setting.
Q1. What does IDMT stand for in protection relays?
- (a) Instant Direct Maximum Time
- (b) Inverse Definite Minimum Time
- (c) Integrated Digital Measuring Transformer
- (d) Induction Delay Minimum Trip
Answer: (b) Inverse Definite Minimum Time — the operating time is inversely related to the fault current, down to a definite minimum time.
Q2. In an IDMT relay, how does the operating time change as the fault current increases?
- (a) It increases
- (b) It decreases
- (c) It stays the same
- (d) It becomes zero instantly
Answer: (b) It decreases — a larger fault current makes the relay operate faster, which is the “inverse” part of IDMT.
Q3. What is the plug setting (PS) of an overcurrent relay?
- (a) The voltage rating of the relay coil
- (b) The pickup current expressed as a percentage of the CT secondary rated current
- (c) The time delay in seconds
- (d) The number of relay contacts
Answer: (b) The pickup current expressed as a percentage of the CT secondary rated current — with a 5 A CT secondary, a 100% plug setting means a 5 A secondary pickup.
Q4. An overcurrent relay is set to 100% plug setting on a 200/5 CT. What is its pickup current?
- (a) 5 A
- (b) 100 A
- (c) 200 A
- (d) 500 A
Answer: (c) 200 A — pickup = plug setting × CT primary rating = 100% × 200 A = 200 A.
Q5. An overcurrent relay is set to 50% plug setting on a 400/5 CT. What is its pickup current?
- (a) 50 A
- (b) 100 A
- (c) 200 A
- (d) 400 A
Answer: (c) 200 A — pickup = 50% × 400 A = 0.5 × 400 = 200 A.
Q6. A fault current of 1,000 A flows through a relay whose pickup current is 200 A. What is the plug setting multiplier (PSM)?
- (a) 2
- (b) 5
- (c) 10
- (d) 200
Answer: (b) 5 — PSM = fault current ÷ pickup current = 1,000 ÷ 200 = 5.
Q7. What is the time multiplier setting (TMS) of an IDMT relay?
- (a) The CT ratio
- (b) A setting that scales the operating time up or down from the standard time-current curve
- (c) The pickup current in amperes
- (d) The number of poles of the breaker
Answer: (b) A setting that scales the operating time up or down from the standard time-current curve — a higher TMS means a longer operating time at the same fault current.
Q8. At a given fault current the standard curve gives an operating time of 2 seconds. If the TMS is set to 0.5, what is the actual operating time?
- (a) 0.5 seconds
- (b) 1 second
- (c) 2 seconds
- (d) 4 seconds
Answer: (b) 1 second — operating time = TMS × curve time = 0.5 × 2 = 1 second.
Q9. What does the “definite minimum time” part of IDMT mean?
- (a) The relay always takes at least one hour to operate
- (b) At very high fault currents the operating time stops falling and levels off at a minimum value
- (c) The relay trips only after a fixed 10-second delay
- (d) The relay never operates below its minimum current
Answer: (b) At very high fault currents the operating time stops falling and levels off at a minimum value — the curve flattens so the time cannot go below this definite minimum.
Q10. An overcurrent relay is set to 125% plug setting on a 200/5 CT. What is its pickup current?
- (a) 125 A
- (b) 200 A
- (c) 250 A
- (d) 325 A
Answer: (c) 250 A — pickup = 125% × 200 A = 1.25 × 200 = 250 A.
Also read: Power Loss Formula | All MCQ Topics