Power System MCQs
10 practice questions on power systems — transmission voltages, why multiples of 11, line losses and substations — with answers and explanations.
Q1. Transmission voltages are multiples of 11 (11 kV, 33 kV, 132 kV) because of the:
- (a) Form factor of 1.11 — the RMS value of a sine wave is 1.11 times its average value
- (b) Number 11 being lucky
- (c) 11 poles in a generator
- (d) 11 wires in a transmission line
Answer: (a) Form factor of 1.11 — the RMS value of a sine wave is 1.11 times its average value, so a 10 kV average becomes 11.1 kV RMS, rounded to 11 kV.
Q2. The same power is transmitted at 132 kV instead of 11 kV. By what factor does the I²R line loss fall?
- (a) 12 times
- (b) 144 times
- (c) 2 times
- (d) 24 times
Answer: (b) 144 times — the current falls by 132 ÷ 11 = 12 times, and loss depends on current squared, so it falls by 12² = 144 times.
Q3. If the transmission voltage is doubled while the power stays the same, the line loss becomes:
- (a) Half
- (b) One-quarter
- (c) The same
- (d) Double
Answer: (b) One-quarter — doubling the voltage halves the current, and loss = I²R, so it becomes (½)² = ¼ of the original loss.
Q4. The standard low-voltage distribution supply to homes is:
- (a) 11 kV three-phase
- (b) 400 V three-phase / 230 V single-phase
- (c) 33 kV three-phase
- (d) 132 kV three-phase
Answer: (b) 400 V three-phase / 230 V single-phase — 400 V between phases gives 230 V between phase and neutral for homes.
Q5. A substation steps voltage down in stages. The usual order is:
- (a) 132 kV → 33 kV → 11 kV → 400 V
- (b) 400 V → 11 kV → 33 kV → 132 kV
- (c) 33 kV → 132 kV → 11 kV → 400 V
- (d) 11 kV → 400 V → 33 kV → 132 kV
Answer: (a) 132 kV → 33 kV → 11 kV → 400 V — each step brings the voltage closer to what homes and shops use.
Q6. Power is transmitted as AC rather than DC mainly because:
- (a) AC wires are cheaper
- (b) Transformers can easily step AC voltage up and down
- (c) AC has no losses
- (d) DC cannot travel in wires
Answer: (b) Transformers can easily step AC voltage up and down — stepping up to 132 kV for transmission and back down to 400 V for use is simple with AC.
Q7. Which of these is NOT a standard transmission voltage (multiple of 11)?
- (a) 33 kV
- (b) 66 kV
- (c) 132 kV
- (d) 25 kV
Answer: (d) 25 kV — 33 kV is 3 × 11, 66 kV is 6 × 11 and 132 kV is 12 × 11; 25 kV is not a multiple of 11.
Q8. Corona loss in a transmission line:
- (a) Falls as the voltage rises
- (b) Rises as the voltage rises, and is worse in wet weather
- (c) Only happens at night
- (d) Does not depend on voltage at all
Answer: (b) Rises as the voltage rises, and is worse in wet weather — above a critical voltage the air around the conductor ionises and leaks energy, with a hissing sound.
Q9. The skin effect means that in an AC conductor:
- (a) The current flows evenly through the whole cross-section
- (b) Most of the current flows near the surface of the conductor
- (c) The current flows only through the centre
- (d) The conductor gets thinner
Answer: (b) Most of the current flows near the surface of the conductor — the effective resistance rises, which is one reason AC conductors are sometimes made hollow or stranded.
Q10. A step-up transformer is used at the generating station to:
- (a) Raise the voltage so the transmission current and I²R loss fall
- (b) Lower the voltage for the transmission lines
- (c) Convert AC to DC
- (d) Increase the frequency to 100 Hz
Answer: (a) Raise the voltage so the transmission current and I²R loss fall — the same power at a higher voltage needs less current, so thinner wires and far less loss.
Also read: Why Are Transmission Voltages 11 kV, 33 kV, 66 kV, 132 kV? | Transformer MCQs | All MCQ Topics