Power Quality MCQs — Set 10
10 practice questions applying power quality knowledge — real installations, real faults, and choosing the right fix.
Q1. Which type of installation is most sensitive to even a short voltage sag?
- (a) A data centre with servers
- (b) A resistive water heater
- (c) A street lighting circuit
- (d) An incandescent lamp circuit
Answer: (a) A data centre with servers — computers and servers can reboot or corrupt data after a dip of only a few cycles, which is why data centres use online UPS systems.
Q2. Why does a variable-frequency drive often trip during a voltage sag?
- (a) The motor overheats instantly
- (b) The DC bus voltage falls below the drive’s undervoltage threshold
- (c) The frequency rises
- (d) The power factor becomes leading
Answer: (b) The DC bus voltage falls below the drive’s undervoltage threshold — the drive rectifies the mains to charge its DC bus, so a sag starves the bus and the drive trips to protect itself.
Q3. A neutral conductor in an office full of computers is running hot. What is the most likely cause?
- (a) Triplen harmonics adding up in the neutral
- (b) A voltage swell
- (c) Low power factor
- (d) A lightning strike
Answer: (a) Triplen harmonics adding up in the neutral — 3rd harmonics from single-phase computer supplies are in phase on all three phases and sum in the neutral, which can overload it.
Q4. What is the usual fix for a neutral overloaded by triplen harmonics?
- (a) Fit an oversized (200%) neutral or install a harmonic filter
- (b) Remove the neutral
- (c) Fit a smaller cable
- (d) Raise the voltage
Answer: (a) Fit an oversized (200%) neutral or install a harmonic filter — a doubled neutral safely carries the summed harmonic current, and a filter removes the harmonics at source.
Q5. A 120 V supply dips to 100 V for 20 ms. Is this a sag?
- (a) No, because it lasted only 20 ms
- (b) Yes, because 100 V is 83% of nominal, below the 90% threshold
- (c) No, because 100 V is above 90 V
- (d) Yes, because any dip is a swell
Answer: (b) Yes, because 100 V is 83% of nominal, below the 90% threshold — 100 ÷ 120 = 83%, and a 20 ms dip is about one cycle, within the sag duration range.
Q6. A load draws a fundamental current of 80 A and a 3rd harmonic current of 12 A. What is the current THD?
- (a) 12%
- (b) 15%
- (c) 10%
- (d) 20%
Answer: (b) 15% — THD = 12 ÷ 80 × 100 = 15%.
Q7. Three phase voltages are 240 V, 235 V and 230 V. What is the voltage unbalance?
- (a) 2.1%
- (b) 4.2%
- (c) 1.0%
- (d) 5.0%
Answer: (a) 2.1% — average = (240 + 235 + 230) ÷ 3 = 235 V; maximum deviation is 5 V; unbalance = 5 ÷ 235 × 100 = 2.1%.
Q8. A factory suffers repeated 200 ms voltage sags that trip its drives. Which mitigation fits best?
- (a) A passive harmonic filter
- (b) A dynamic voltage restorer (DVR) or online UPS
- (c) A surge arrester
- (d) A bigger fuse
Answer: (b) A dynamic voltage restorer (DVR) or online UPS — a DVR injects the missing voltage during the sag, and an online UPS rides through it entirely; a harmonic filter does nothing for sags.
Q9. A welding shop causes flicker in neighbouring premises. What is the best mitigation?
- (a) A dedicated transformer or feeder for the welder, or a fast reactive compensator
- (b) A surge arrester
- (c) A bigger circuit breaker
- (d) More lighting
Answer: (a) A dedicated transformer or feeder for the welder, or a fast reactive compensator — separating the fluctuating load from other users stops its voltage swings reaching them.
Q10. What is the correct first step when a site reports power quality problems?
- (a) Buy the most expensive filter available
- (b) Measure and record the supply with a power quality analyser before choosing any fix
- (c) Replace all the cables
- (d) Increase the tariff
Answer: (b) Measure and record the supply with a power quality analyser before choosing any fix — you cannot fix what you have not measured; the recording shows whether the problem is sags, harmonics, unbalance or flicker, and each needs a different solution.
Also read: Separately Excited DC Motor | All MCQ Topics