Power Quality MCQs — Set 5
10 practice questions on harmonics and total harmonic distortion — where harmonics come from and what they do.
Q1. Which of these loads produces harmonics?
- (a) A resistive heater
- (b) A variable-frequency drive (VFD)
- (c) An incandescent lamp
- (d) A kettle
Answer: (b) A variable-frequency drive (VFD) — VFDs, rectifiers, SMPS units and LED drivers are non-linear loads that draw current in pulses, creating harmonics.
Q2. On a 50 Hz system, what is the frequency of the 3rd harmonic?
- (a) 50 Hz
- (b) 100 Hz
- (c) 150 Hz
- (d) 300 Hz
Answer: (c) 150 Hz — the 3rd harmonic is 3 × 50 Hz = 150 Hz.
Q3. On a 60 Hz system, what is the frequency of the 5th harmonic?
- (a) 60 Hz
- (b) 120 Hz
- (c) 180 Hz
- (d) 300 Hz
Answer: (d) 300 Hz — the 5th harmonic is 5 × 60 Hz = 300 Hz.
Q4. A load draws a fundamental current of 200 A, a 3rd harmonic of 20 A and a 5th harmonic of 10 A. What is the current THD?
- (a) 15%
- (b) 5%
- (c) 11.2%
- (d) 22.4%
Answer: (c) 11.2% — THD = √(20² + 10²) ÷ 200 × 100 = √500 ÷ 200 × 100 = 22.36 ÷ 200 × 100 = 11.2%.
Q5. A load draws a fundamental current of 100 A, a 3rd harmonic of 15 A and a 5th harmonic of 12 A. What is the current THD?
- (a) 27%
- (b) 19.2%
- (c) 15%
- (d) 12%
Answer: (b) 19.2% — THD = √(15² + 12²) ÷ 100 × 100 = √369 ÷ 100 × 100 = 19.21 ÷ 100 × 100 = 19.2%.
Q6. Why can the neutral conductor in a building full of computers carry more current than a phase conductor?
- (a) Because the neutral is always thicker
- (b) Because triplen (3rd, 9th) harmonics add up in the neutral instead of cancelling
- (c) Because the neutral carries the supply voltage
- (d) Because computers use DC only
Answer: (b) Because triplen (3rd, 9th) harmonics add up in the neutral instead of cancelling — balanced fundamental currents cancel in the neutral, but 3rd harmonics from all three phases are in phase and add together.
Q7. What is the IEEE 519 recommended limit for total voltage harmonic distortion (THDv) on a general low-voltage system?
- (a) 1%
- (b) 5%
- (c) 10%
- (d) 20%
Answer: (b) 5% — IEEE 519 recommends keeping total voltage distortion at or below 5% for systems up to 1 kV.
Q8. Which of these is a harmful effect of harmonics on a transformer?
- (a) Reduced weight
- (b) Extra eddy-current and hysteresis losses causing overheating
- (c) Higher power factor
- (d) Lower voltage drop
Answer: (b) Extra eddy-current and hysteresis losses causing overheating — harmonic currents raise core and winding losses, so a heavily distorted load can overheat a transformer rated for sinusoidal current.
Q9. Why are even-order harmonics (2nd, 4th, 6th) usually very small in practice?
- (a) They are absorbed by the earth
- (b) Most loads draw current symmetrically in both half-cycles, which cancels even harmonics
- (c) They are blocked by circuit breakers
- (d) They only exist on DC systems
Answer: (b) Most loads draw current symmetrically in both half-cycles, which cancels even harmonics — half-wave symmetry means even harmonics are near zero; odd harmonics dominate.
Q10. What is a K-factor rated transformer designed for?
- (a) Feeding only resistive loads
- (b) Supplying non-linear loads with high harmonic currents without overheating
- (c) Stepping voltage up to 11 kV
- (d) Measuring power factor
Answer: (b) Supplying non-linear loads with high harmonic currents without overheating — K-rated transformers have a larger neutral, lower-loss core and windings built to handle harmonic heating.
Also read: Power Loss Formula | All MCQ Topics