Power Quality MCQs — Set 1
10 practice questions on what power quality means, voltage sags and swells, harmonics and voltage unbalance — with worked answers.
Q1. What does “power quality” mean in an electrical supply?
- (a) How cheap the electricity is
- (b) How closely the voltage, frequency and waveform match the ideal supply
- (c) How many units of energy are consumed
- (d) How fast the meter runs
Answer: (b) How closely the voltage, frequency and waveform match the ideal supply — good power quality means a steady sinusoidal voltage at the rated value and frequency, free from sags, harmonics and interruptions.
Q2. A 230 V supply dips to 180 V for a few cycles. What is this event called?
- (a) A swell
- (b) An interruption
- (c) A voltage sag
- (d) A transient
Answer: (c) A voltage sag — a sag is a dip below 90% of nominal voltage. 90% of 230 V is 207 V, and 180 V is below that, so it is a sag.
Q3. On a 230 V system, a voltage rise to 260 V lasting several cycles is best described as what?
- (a) A voltage swell
- (b) A voltage sag
- (c) An interruption
- (d) Flicker
Answer: (a) A voltage swell — a swell is a rise above 110% of nominal voltage. 110% of 230 V is 253 V, and 260 V exceeds it.
Q4. The voltage on a feeder falls to zero for 2 seconds and then returns. What is this?
- (a) A sag
- (b) A momentary interruption
- (c) A swell
- (d) A harmonic
Answer: (b) A momentary interruption — an interruption is a drop to near zero (below 10% of nominal); one lasting from 0.5 cycle to 3 s is classed as momentary.
Q5. A very short, sharp spike of voltage lasting only microseconds is called what?
- (a) Flicker
- (b) A sag
- (c) An impulsive transient
- (d) An undervoltage
Answer: (c) An impulsive transient — a sudden, short-lived spike, often caused by lightning or switching, lasting microseconds to a few milliseconds.
Q6. Rapid, repeated small changes in voltage that make lamps visibly brighten and dim are known as what?
- (a) Flicker
- (b) Harmonics
- (c) A swell
- (d) An interruption
Answer: (a) Flicker — flicker is the visible lamp brightness variation caused by rapid voltage fluctuations, often from arc furnaces or welders.
Q7. Harmonics in a power system are currents or voltages at what frequencies?
- (a) Random frequencies below 50 Hz
- (b) Whole-number multiples of the fundamental frequency
- (c) Exactly half the fundamental frequency
- (d) Only the supply frequency itself
Answer: (b) Whole-number multiples of the fundamental frequency — on a 50 Hz system the 3rd harmonic is 150 Hz, the 5th is 250 Hz, and so on.
Q8. A load draws a fundamental current of 50 A and a 3rd harmonic current of 10 A. What is the current THD?
- (a) 10%
- (b) 20%
- (c) 5%
- (d) 25%
Answer: (b) 20% — THD = harmonic current ÷ fundamental × 100 = 10 ÷ 50 × 100 = 20%.
Q9. Three phase voltages are 230 V, 225 V and 220 V. What is the voltage unbalance?
- (a) 2.2%
- (b) 4.4%
- (c) 1.1%
- (d) 5.0%
Answer: (a) 2.2% — average = (230 + 225 + 220) ÷ 3 = 225 V; maximum deviation from average is 5 V; unbalance = 5 ÷ 225 × 100 = 2.2%.
Q10. A non-linear load draws a distorted current. How does its true power factor compare with its displacement power factor?
- (a) True power factor is higher
- (b) True power factor is lower
- (c) They are always equal
- (d) True power factor is always 1
Answer: (b) True power factor is lower — displacement power factor considers only the fundamental, while true power factor includes the harmonic distortion, so harmonics always pull the true power factor down.
Also read: Power Loss Formula | All MCQ Topics