Power Factor Correction MCQs — Set 6

10 practice questions on capacitor banks and APFC panels — where to fit them, how they switch, and how they stay safe.

Q1. For the best reduction in cable losses, a capacitor bank should be installed:

  • (a) At the supply substation only
  • (b) As close as possible to the inductive load it corrects
  • (c) In series with the load
  • (d) On the DC side of the circuit

Answer: (b) As close as possible to the inductive load it corrects — local correction keeps the reactive current out of the cables between the bank and the load.

Q2. What does an APFC panel do that a fixed capacitor bank cannot?

  • (a) It generates real power
  • (b) It switches capacitor steps in and out automatically as the load changes
  • (c) It works only on DC supplies
  • (d) It replaces the transformer

Answer: (b) It switches capacitor steps in and out automatically as the load changes — the controller keeps the power factor near its target under varying load.

Q3. A fixed capacitor bank is most suitable for which situation?

  • (a) A load that changes every few seconds
  • (b) A steady, constant load such as a continuously running motor
  • (c) A load that is switched off most of the day
  • (d) A purely resistive load

Answer: (b) A steady, constant load such as a continuously running motor — fixed capacitors suit constant loads; varying loads need automatic switching.

Q4. Power factor correction capacitors are connected to the supply in:

  • (a) Series with the load
  • (b) Parallel with the load
  • (c) Series with the transformer primary
  • (d) Parallel with the earth wire

Answer: (b) Parallel with the load — shunt capacitors supply reactive current locally without interrupting the load current path.

Q5. A 60 kVAR capacitor bank is built in 6 equal steps. What is the rating of each step?

  • (a) 6 kVAR
  • (b) 60 kVAR
  • (c) 10 kVAR
  • (d) 30 kVAR

Answer: (c) 10 kVAR — 60 ÷ 6 = 10 kVAR per step, so the APFC controller can add correction in 10 kVAR blocks.

Q6. Why is a discharge resistor fitted across a power factor correction capacitor?

  • (a) To increase the capacitance
  • (b) To discharge the capacitor to a safe voltage after it is disconnected
  • (c) To raise the power factor further
  • (d) To limit the load current

Answer: (b) To discharge the capacitor to a safe voltage after it is disconnected — a charged capacitor can hold a dangerous voltage long after switch-off.

Q7. A capacitor is rated 20 kVAR at 400 V. If it is operated at 200 V, what kVAR will it actually deliver?

  • (a) 20 kVAR
  • (b) 10 kVAR
  • (c) 5 kVAR
  • (d) 40 kVAR

Answer: (c) 5 kVAR — capacitor kVAR varies with the square of the voltage: (200 ÷ 400)² = 0.25, so 20 × 0.25 = 5 kVAR.

Q8. What is the current drawn by a 30 kVAR three-phase capacitor bank at 400 V?

  • (a) 75 A
  • (b) 43.3 A
  • (c) 30 A
  • (d) 25 A

Answer: (b) 43.3 A — I = kVAR × 1000 ÷ (√3 × V) = 30,000 ÷ (1.732 × 400) = 43.3 A.

Q9. What is the current drawn by a 15 kVAR three-phase capacitor bank at 400 V?

  • (a) 43.3 A
  • (b) 15 A
  • (c) 21.7 A
  • (d) 37.5 A

Answer: (c) 21.7 A — I = 15,000 ÷ (1.732 × 400) = 21.7 A, exactly half the current of a 30 kVAR bank at the same voltage.

Q10. What does the controller of an APFC panel measure to decide how many capacitor steps to switch in?

  • (a) Only the supply voltage
  • (b) The load current and its phase angle, via a current transformer
  • (c) Only the room temperature
  • (d) The resistance of the cables

Answer: (b) The load current and its phase angle, via a current transformer — the controller compares voltage and current (from a CT) to work out the actual power factor.

Also read: Power Loss Formula | All MCQ Topics