Power Factor Correction MCQs — Set 6
10 practice questions on capacitor banks and APFC panels — where to fit them, how they switch, and how they stay safe.
Q1. For the best reduction in cable losses, a capacitor bank should be installed:
- (a) At the supply substation only
- (b) As close as possible to the inductive load it corrects
- (c) In series with the load
- (d) On the DC side of the circuit
Answer: (b) As close as possible to the inductive load it corrects — local correction keeps the reactive current out of the cables between the bank and the load.
Q2. What does an APFC panel do that a fixed capacitor bank cannot?
- (a) It generates real power
- (b) It switches capacitor steps in and out automatically as the load changes
- (c) It works only on DC supplies
- (d) It replaces the transformer
Answer: (b) It switches capacitor steps in and out automatically as the load changes — the controller keeps the power factor near its target under varying load.
Q3. A fixed capacitor bank is most suitable for which situation?
- (a) A load that changes every few seconds
- (b) A steady, constant load such as a continuously running motor
- (c) A load that is switched off most of the day
- (d) A purely resistive load
Answer: (b) A steady, constant load such as a continuously running motor — fixed capacitors suit constant loads; varying loads need automatic switching.
Q4. Power factor correction capacitors are connected to the supply in:
- (a) Series with the load
- (b) Parallel with the load
- (c) Series with the transformer primary
- (d) Parallel with the earth wire
Answer: (b) Parallel with the load — shunt capacitors supply reactive current locally without interrupting the load current path.
Q5. A 60 kVAR capacitor bank is built in 6 equal steps. What is the rating of each step?
- (a) 6 kVAR
- (b) 60 kVAR
- (c) 10 kVAR
- (d) 30 kVAR
Answer: (c) 10 kVAR — 60 ÷ 6 = 10 kVAR per step, so the APFC controller can add correction in 10 kVAR blocks.
Q6. Why is a discharge resistor fitted across a power factor correction capacitor?
- (a) To increase the capacitance
- (b) To discharge the capacitor to a safe voltage after it is disconnected
- (c) To raise the power factor further
- (d) To limit the load current
Answer: (b) To discharge the capacitor to a safe voltage after it is disconnected — a charged capacitor can hold a dangerous voltage long after switch-off.
Q7. A capacitor is rated 20 kVAR at 400 V. If it is operated at 200 V, what kVAR will it actually deliver?
- (a) 20 kVAR
- (b) 10 kVAR
- (c) 5 kVAR
- (d) 40 kVAR
Answer: (c) 5 kVAR — capacitor kVAR varies with the square of the voltage: (200 ÷ 400)² = 0.25, so 20 × 0.25 = 5 kVAR.
Q8. What is the current drawn by a 30 kVAR three-phase capacitor bank at 400 V?
- (a) 75 A
- (b) 43.3 A
- (c) 30 A
- (d) 25 A
Answer: (b) 43.3 A — I = kVAR × 1000 ÷ (√3 × V) = 30,000 ÷ (1.732 × 400) = 43.3 A.
Q9. What is the current drawn by a 15 kVAR three-phase capacitor bank at 400 V?
- (a) 43.3 A
- (b) 15 A
- (c) 21.7 A
- (d) 37.5 A
Answer: (c) 21.7 A — I = 15,000 ÷ (1.732 × 400) = 21.7 A, exactly half the current of a 30 kVAR bank at the same voltage.
Q10. What does the controller of an APFC panel measure to decide how many capacitor steps to switch in?
- (a) Only the supply voltage
- (b) The load current and its phase angle, via a current transformer
- (c) Only the room temperature
- (d) The resistance of the cables
Answer: (b) The load current and its phase angle, via a current transformer — the controller compares voltage and current (from a CT) to work out the actual power factor.