PLC Basics MCQs — Set 7
10 practice questions on latching and seal-in circuits — start-stop control, interlocking and latch/unlatch instructions — with answers and explanations.
Q1. What is a seal-in (latching) circuit in ladder logic?
- (a) A circuit that delays the output by 10 seconds
- (b) A circuit where an NO contact of the output is wired in parallel with the start button, so the output stays on after the button is released
- (c) A circuit that counts pulses
- (d) A circuit that switches the PLC off
Answer: (b) A circuit where an NO contact of the output is wired in parallel with the start button, so the output stays on after the button is released — the output “seals itself in”.
Q2. In a start-stop motor circuit, how are the start and stop pushbuttons wired in the rung?
- (a) Both NO contacts in parallel
- (b) NO start contact in parallel with the seal-in contact, and an NC stop contact in series with them
- (c) Both NC contacts in series
- (d) The stop button is not used in the rung at all
Answer: (b) NO start contact in parallel with the seal-in contact, and an NC stop contact in series with them — start seals the rung in, stop breaks it.
Q3. In a seal-in circuit, what breaks the latch and stops the motor?
- (a) Pressing the start button again
- (b) Pressing the stop button, which opens the NC contact in series with the rung
- (c) Releasing the start button
- (d) The scan cycle ending
Answer: (b) Pressing the stop button, which opens the NC contact in series with the rung — releasing the start button does nothing because the seal-in contact holds the rung true.
Q4. What do the OTL (latch) and OTU (unlatch) instructions do?
- (a) OTL sets an output ON and it stays ON until an OTU instruction for the same address turns it OFF
- (b) OTL turns an output OFF permanently
- (c) OTL counts up and OTU counts down
- (d) OTL delays the output and OTU speeds it up
Answer: (a) OTL sets an output ON and it stays ON until an OTU instruction for the same address turns it OFF — unlike a normal coil, a latched output stays set even when its rung goes false.
Q5. After an output is set by an OTL instruction, what turns it off?
- (a) The rung going false
- (b) Only an OTU instruction for the same output address
- (c) The next scan cycle
- (d) Pressing any pushbutton
Answer: (b) Only an OTU instruction for the same output address — a latched output ignores its rung going false; it needs an explicit unlatch.
Q6. What is interlocking in PLC control?
- (a) Locking the PLC cabinet door
- (b) Using an NC contact of one output in another output’s rung so the two outputs cannot be ON at the same time
- (c) Connecting two PLCs together
- (d) Delaying both outputs by the same timer
Answer: (b) Using an NC contact of one output in another output’s rung so the two outputs cannot be ON at the same time — a safety measure for outputs that must never run together.
Q7. Why must forward and reverse motor contactors be interlocked?
- (a) To make the motor run faster
- (b) To prevent both contactors closing at once, which would short-circuit the supply
- (c) To save electricity
- (d) To reduce the scan time
Answer: (b) To prevent both contactors closing at once, which would short-circuit the supply — the NC contact of the forward output in the reverse rung (and vice versa) blocks simultaneous operation.
Q8. A motor is started with a momentary pushbutton and a seal-in circuit. The operator releases the start button. What happens?
- (a) The motor stops immediately
- (b) The motor keeps running, because the seal-in contact holds the rung true
- (c) The motor reverses
- (d) The PLC faults
Answer: (b) The motor keeps running, because the seal-in contact holds the rung true — that is the whole point of the seal-in: a brief press starts the motor and it stays running.
Q9. In a seal-in motor circuit, the seal-in contact welds closed. What is the likely result?
- (a) The motor runs faster
- (b) The motor cannot be stopped by the stop button, because the welded contact keeps the rung true
- (c) The motor stops by itself
- (d) The PLC program is erased
Answer: (b) The motor cannot be stopped by the stop button, because the welded contact keeps the rung true — a welded seal-in contact bypasses the stop, which is a dangerous fault to check for.
Q10. Where is the seal-in contact wired in a start-stop rung?
- (a) In series with the stop button
- (b) In parallel with the start pushbutton
- (c) Across the power rails
- (d) In the output module
Answer: (b) In parallel with the start pushbutton — when the output energises, its own contact closes across the start button and takes over holding the rung true.