NEC Code MCQs — Set 10

10 mixed practice questions reviewing the NEC — voltage drop, receptacles, box fill, cable support and service rules.

Q1. What is the NEC recommended maximum voltage drop for a branch circuit?

  • (a) 1%
  • (b) 3%
  • (c) 5%
  • (d) 10%

Answer: (b) 3% — the fine print note in NEC 210.19(A)(1) recommends no more than 3% voltage drop on a branch circuit.

Q2. What is the NEC recommended maximum total voltage drop from service to the farthest outlet?

  • (a) 3%
  • (b) 5%
  • (c) 8%
  • (d) 10%

Answer: (b) 5% — the NEC recommends 3% on the branch circuit and 5% total (feeder plus branch circuit) for reasonable efficiency.

Q3. What kind of receptacles must be installed in dwelling units under NEC 406.12?

  • (a) GFCI receptacles everywhere
  • (b) Tamper-resistant receptacles
  • (c) Isolated-ground receptacles
  • (d) 30 A receptacles

Answer: (b) Tamper-resistant receptacles — NEC 406.12 requires tamper-resistant receptacles in dwellings to protect children from inserting objects into the slots.

Q4. A 4,500 W electric water heater runs on 240 V continuously. What is the minimum breaker size?

  • (a) 20 A
  • (b) 25 A
  • (c) 30 A
  • (d) 40 A

Answer: (b) 25 A — the heater draws 4,500 ÷ 240 = 18.75 A, and as a continuous load it needs a breaker rated at 18.75 × 1.25 = 23.4 A, so the next standard size is 25 A.

Q5. Which rooms must have a wall-switch-controlled lighting outlet under NEC 210.70?

  • (a) Bathrooms only
  • (b) Habitable rooms, hallways, stairways, garages and bathrooms
  • (c) Bedrooms only
  • (d) Kitchens only

Answer: (b) Habitable rooms, hallways, stairways, garages and bathrooms — NEC 210.70 requires a wall-switch-controlled lighting outlet in every habitable room and in hallways, stairways, attached garages and bathrooms.

Q6. The NEC sets no maximum number of receptacles on a residential general-purpose branch circuit. Why is this safe?

  • (a) Because receptacles never draw current
  • (b) Because the breaker protects the circuit regardless of how many receptacles are on it
  • (c) Because the NEC forbids plugging anything in
  • (d) Because residential circuits are always 30 A

Answer: (b) Because the breaker protects the circuit regardless of how many receptacles are on it — the load is limited by what is plugged in and by the breaker, so the NEC limits the circuit rating, not the receptacle count, in dwellings.

Q7. In box fill calculations (NEC 314.16), how many volume units does each current-carrying conductor count as?

  • (a) Half a unit
  • (b) One unit
  • (c) Two units
  • (d) Three units

Answer: (b) One unit — each conductor entering a box counts as one volume allowance, while devices count as two and ground wires together count as one.

Q8. NM (Romex) cable must be secured within what distance of a box and at what maximum interval along its run?

  • (a) Within 6 in of a box and every 2 ft
  • (b) Within 12 in of a box and every 4.5 ft
  • (c) Within 18 in of a box and every 6 ft
  • (d) Within 24 in of a box and every 8 ft

Answer: (b) Within 12 in of a box and every 4.5 ft — NEC 334.30 requires NM cable to be secured within 12 in of every box and at intervals of no more than 4.5 ft.

Q9. A 12 AWG copper conductor with 60°C terminations is rated for what maximum current under NEC Table 310.16?

  • (a) 15 A
  • (b) 20 A
  • (c) 25 A
  • (d) 30 A

Answer: (b) 20 A — 12 AWG copper is rated 20 A at 60°C, which is why it is used on 20 A branch circuits.

Q10. Since the 2020 NEC, what must be provided outside a dwelling for emergency use?

  • (a) An outdoor receptacle only
  • (b) An emergency disconnect, readily accessible outdoors
  • (c) A second service panel
  • (d) A lightning rod

Answer: (b) An emergency disconnect, readily accessible outdoors — NEC 230.85 requires an emergency disconnect outside a one- or two-family dwelling so first responders can cut power quickly.