Motor Starter MCQs — Set 10

10 practice questions on choosing the right starter for the load — soft starter, VFD, star-delta and auto-transformer compared, plus reversing and DC motor starters — with answers and explanations.

Q1. A fixed-speed centrifugal pump has low starting torque and the budget is tight. Which starter is the best choice?

  • (a) VFD
  • (b) Soft starter
  • (c) Rotor resistance starter
  • (d) 3-point starter

Answer: (b) Soft starter — it gives a gentle start at roughly a third of the price of a VFD, and no speed control is needed for a fixed-speed pump.

Q2. A fan whose flow must vary through the day, where energy saving matters. Which is the best choice?

  • (a) DOL starter
  • (b) Star-delta starter
  • (c) VFD
  • (d) Auto-transformer starter

Answer: (c) VFD — only the VFD varies speed while running, and the affinity law means a fan at 80% speed needs only about 51% of the power.

Q3. A medium-size motor starts on no load, cost matters, and one third of the delta starting torque is enough. Which starter is the best choice?

  • (a) Star-delta starter
  • (b) VFD
  • (c) Rotor resistance starter
  • (d) Soft starter with a 40% initial voltage

Answer: (a) Star-delta starter — it is cheap, simple and reliable, and 1/3 starting torque is plenty for an unloaded start.

Q4. How does a reversing starter change a motor’s direction of rotation?

  • (a) It swaps the star and delta connections
  • (b) Two contactors swap two of the supply phases, with mechanical and electrical interlocks to prevent both closing together
  • (c) It reverses the polarity of the DC supply
  • (d) It changes the supply frequency

Answer: (b) Two contactors swap two of the supply phases, with mechanical and electrical interlocks to prevent both closing together — closing both at once would short-circuit the supply.

Q5. Which starter is used for a DC shunt motor?

  • (a) Star-delta starter
  • (b) 3-point (faceplate) starter, with a no-volt coil
  • (c) Soft starter
  • (d) Auto-transformer starter

Answer: (b) 3-point (faceplate) starter, with a no-volt coil — it inserts resistance in the armature circuit at starting and the no-volt coil drops the starter out if the supply fails.

Q6. A part-winding starter works by:

  • (a) Starting the motor on one of its two parallel stator windings, then connecting the second winding
  • (b) Connecting the motor in star, then delta
  • (c) Adding resistance to the rotor circuit
  • (d) Ramping the frequency from zero

Answer: (a) Starting the motor on one of its two parallel stator windings, then connecting the second winding — the first step draws about half the normal starting current.

Q7. A primary resistance starter reduces the starting current by:

  • (a) Resistors in series with the stator, shorted out in steps as the motor runs up
  • (b) A tapped transformer in series with the motor
  • (c) Thyristors that chop the supply voltage
  • (d) Connecting the motor in star

Answer: (a) Resistors in series with the stator, shorted out in steps as the motor runs up — the resistors drop some of the voltage at starting, then are bypassed.

Q8. A crusher needs full torque from the first turn and a gentle start on a weak supply. Which is the best choice?

  • (a) Soft starter
  • (b) Star-delta starter
  • (c) VFD — it delivers full rated torque at a starting current of only 1.0–1.5 × full-load current
  • (d) DOL starter

Answer: (c) VFD — it delivers full rated torque at a starting current of only 1.0–1.5 × full-load current — the soft starter and star-delta cannot give full torque at starting.

Q9. Compared with star-delta’s 33% starting torque, what does a 65% auto-transformer tap give?

  • (a) About 25% starting torque
  • (b) About 33% starting torque
  • (c) About 42% starting torque
  • (d) About 65% starting torque

Answer: (c) About 42% starting torque — torque varies with voltage squared, so 0.65² = 0.4225, which is more than star-delta’s 33% and can start a heavier load.

Q10. A motor must start and stop many times per hour. What must the starter choice take into account?

  • (a) Nothing — all starters handle unlimited starts
  • (b) Frequent starts heat soft-starter thyristors and wear DOL contactors, so the starter must be rated for the starts-per-hour duty
  • (c) Only the colour of the starter enclosure
  • (d) The motor will draw less current with each start

Answer: (b) Frequent starts heat soft-starter thyristors and wear DOL contactors, so the starter must be rated for the starts-per-hour duty — repeated starts are a thermal and wear limit, not a free choice.