Motor Starter MCQs — Set 7

10 practice questions on starting a motor with a VFD — frequency and voltage ramp, low starting current, full torque, and speed control after the start — with answers and explanations.

Q1. With a VFD, the starting current of an induction motor is only about:

  • (a) 6–8 × full-load current
  • (b) 3–4 × full-load current
  • (c) 1.0–1.5 × full-load current
  • (d) 10 × full-load current

Answer: (c) 1.0–1.5 × full-load current — the VFD ramps frequency and voltage together, so there is no inrush in the DOL sense.

Q2. What does a VFD do to the supply before feeding the motor?

  • (a) It steps the voltage up with a transformer
  • (b) It rectifies the AC to DC, then inverts it back to variable-frequency AC using PWM
  • (c) It adds resistance in series with the motor
  • (d) It connects the motor in star, then delta

Answer: (b) It rectifies the AC to DC, then inverts it back to variable-frequency AC using PWM — because it rebuilds the supply, it controls both voltage and frequency.

Q3. Synchronous speed Ns = 120 × f ÷ P. A 4-pole motor on a 50 Hz supply has a synchronous speed of:

  • (a) 750 rpm
  • (b) 1000 rpm
  • (c) 1500 rpm
  • (d) 3000 rpm

Answer: (c) 1500 rpm — Ns = 120 × 50 ÷ 4 = 1500 rpm.

Q4. In a star-delta starter, the starting current of a three-phase motor is reduced to what fraction of the direct-on-line (DOL) starting current?

  • (a) 1/2
  • (b) 1/3
  • (c) 1/6
  • (d) 2/3

Answer: (b) 1/3 — a star-delta starter cuts both the starting current and the starting torque to one-third of the direct-on-line values.

Q5. For a centrifugal fan, power follows the cube of speed. At 80% speed the fan needs about how much power?

  • (a) 80% of full power
  • (b) 64% of full power
  • (c) 51% of full power
  • (d) 20% of full power

Answer: (c) 51% of full power — power varies with speed cubed, so 0.80³ = 0.512, about 51%.

Q6. A 4-pole motor is run from a VFD at 30 Hz. What is its synchronous speed?

  • (a) 900 rpm
  • (b) 1200 rpm
  • (c) 1500 rpm
  • (d) 600 rpm

Answer: (a) 900 rpm — Ns = 120 × 30 ÷ 4 = 900 rpm.

Q7. Unlike a soft starter, a VFD at starting can deliver:

  • (a) Only 16% of rated torque
  • (b) Only 33% of rated torque
  • (c) Full rated torque, 100–150% of rated torque
  • (d) No torque at all until full speed

Answer: (c) Full rated torque, 100–150% of rated torque — because it controls frequency as well as voltage, it has no reduced-voltage torque penalty.

Q8. Which is a real drawback of using a VFD as a starter?

  • (a) It cannot start a motor at all
  • (b) It generates harmonics that may need filters, and it costs roughly 2–3 times as much as a soft starter
  • (c) It draws 6–8 × full-load current at starting
  • (d) It can only run the motor at one fixed speed

Answer: (b) It generates harmonics that may need filters, and it costs roughly 2–3 times as much as a soft starter — the price of full speed control.

Q9. When is a DOL starter the right choice for a three-phase motor?

  • (a) When the motor is small and the supply can take the full starting current
  • (b) When the motor must start slowly under a heavy load
  • (c) When the motor must run at variable speed
  • (d) When the supply is too weak for the starting current

Answer: (a) When the motor is small and the supply can take the full starting current — a DOL starter connects the motor straight to the supply, so it suits small motors whose high starting current the supply can handle; larger motors need a reduced-voltage starter.

Q10. A fan running at 50% speed through a VFD needs about how much power?

  • (a) 50% of full power
  • (b) 25% of full power
  • (c) 12.5% of full power
  • (d) 75% of full power

Answer: (c) 12.5% of full power — power varies with speed cubed, so 0.50³ = 0.125, or 12.5%.

Also read: VFD vs Soft Starter | All MCQ Topics