Motor Starter MCQs — Set 6

10 practice questions on the soft starter — thyristor voltage ramp, current limiting, the bypass contactor, and why its starting torque is limited — with answers and explanations.

Q1. What switching device does a soft starter use in each of the three phases?

  • (a) A pair of back-to-back thyristors (SCRs)
  • (b) A mechanical contactor only
  • (c) A diode bridge
  • (d) A tapped transformer

Answer: (a) A pair of back-to-back thyristors (SCRs) — delaying their firing angle within each AC cycle cuts the voltage the motor sees.

Q2. During starting, a soft starter ramps the motor voltage from typically:

  • (a) 0% straight to 100% in one step
  • (b) 30% to 70% of line voltage up to full voltage over a ramp time of a few seconds
  • (c) 100% down to 30% over a few seconds
  • (d) 50 Hz down to 5 Hz

Answer: (b) 30% to 70% of line voltage up to full voltage over a ramp time of a few seconds — the smooth ramp is what makes the start “soft”.

Q3. With a soft starter, the starting current is typically limited to:

  • (a) 1.0–1.5 × full-load current
  • (b) 2–4 × full-load current, typically 3–4×
  • (c) 6–8 × full-load current
  • (d) Exactly the full-load current

Answer: (b) 2–4 × full-load current, typically 3–4× — far below the 6–8× of a direct-on-line start, but well above a VFD’s 1.0–1.5×.

Q4. A soft starter starts a motor at 40% of line voltage. Its starting torque is about:

  • (a) 40% of the DOL starting torque
  • (b) 16% of the DOL starting torque
  • (c) 60% of the DOL starting torque
  • (d) 80% of the DOL starting torque

Answer: (b) 16% of the DOL starting torque — torque varies with voltage squared, so 0.40² = 0.16, or 16%.

Q5. What does the bypass contactor do in a soft starter?

  • (a) It disconnects the motor at full speed
  • (b) It closes at full speed, taking the thyristors out of circuit so the motor runs direct-on-line at about 99.5% efficiency
  • (c) It limits the current during the ramp
  • (d) It reverses the motor

Answer: (b) It closes at full speed, taking the thyristors out of circuit so the motor runs direct-on-line at about 99.5% efficiency — the thyristors only work during the ramp.

Q6. Can a soft starter control the motor’s speed while it is running?

  • (a) Yes, over the full range from zero to full speed
  • (b) No — once the ramp finishes the motor runs at one fixed speed, the line frequency
  • (c) Yes, but only below half speed
  • (d) Yes, if the bypass contactor is left open

Answer: (b) No — once the ramp finishes the motor runs at one fixed speed, the line frequency — a soft starter is a starting device only; speed control needs a VFD.

Q7. A motor has a full-load current of 20 A and the soft starter current limit is set to 3 × full-load current. What is the maximum starting current?

  • (a) 20 A
  • (b) 40 A
  • (c) 60 A
  • (d) 120 A

Answer: (c) 60 A — the limit is 3 × FLC, so 3 × 20 = 60 A.

Q8. A soft starter’s smooth stop is especially useful for which load?

  • (a) A crusher
  • (b) A centrifugal pump, because it prevents water hammer in the pipes
  • (c) A crane hoist
  • (d) A loaded conveyor

Answer: (b) A centrifugal pump, because it prevents water hammer in the pipes — ramping the voltage down stops the pump gently instead of slamming the flow to a halt.

Q9. A soft starter ramps the voltage to 70% of line voltage. The starting torque at that point is about:

  • (a) 70% of the DOL starting torque
  • (b) 49% of the DOL starting torque
  • (c) 30% of the DOL starting torque
  • (d) 84% of the DOL starting torque

Answer: (b) 49% of the DOL starting torque — torque varies with voltage squared, so 0.70² = 0.49, or 49%.

Q10. Why is a soft starter a poor choice for a loaded conveyor or a crusher?

  • (a) It costs more than a VFD
  • (b) It gives only low starting torque, because torque falls with voltage squared, and it cannot supply the high breakaway torque these loads need
  • (c) It draws more current than a DOL start
  • (d) It cannot start a three-phase motor at all

Answer: (b) It gives only low starting torque, because torque falls with voltage squared, and it cannot supply the high breakaway torque these loads need — a VFD or a high-tap auto-transformer starter suits them better.

Also read: VFD vs Soft Starter | All MCQ Topics