Motor Starter MCQs — Set 5
10 practice questions on the auto-transformer starter — tapped reduced voltage, torque proportional to voltage squared, and line current at each tap — with answers and explanations.
Q1. How does an auto-transformer starter reduce the motor voltage at starting?
- (a) By adding resistance in series with the stator
- (b) By connecting a tapped auto-transformer in series with the motor during starting
- (c) By lowering the supply frequency
- (d) By connecting the motor in star
Answer: (b) By connecting a tapped auto-transformer in series with the motor during starting — the tap sets the fraction of line voltage the motor receives.
Q2. Motor torque is proportional to the square of the voltage. At a 50% tap, the starting torque is what fraction of the direct-on-line starting torque?
- (a) 50%
- (b) 25%
- (c) 75%
- (d) 10%
Answer: (b) 25% — torque varies with voltage squared, so 0.50² = 0.25, or 25% of the DOL starting torque.
Q3. A motor has a direct-on-line starting current of 120 A. With an auto-transformer starter on the 50% tap, what is the line current at starting?
- (a) 120 A
- (b) 60 A
- (c) 30 A
- (d) 15 A
Answer: (c) 30 A — the line current is the tap fraction squared times the DOL current, so 0.50² × 120 = 0.25 × 120 = 30 A.
Q4. At a 65% tap, the starting torque of a motor on an auto-transformer starter is about:
- (a) 65% of the DOL starting torque
- (b) 42% of the DOL starting torque
- (c) 33% of the DOL starting torque
- (d) 85% of the DOL starting torque
Answer: (b) 42% of the DOL starting torque — torque varies with voltage squared, so 0.65² = 0.4225, about 42%.
Q5. A motor has a direct-on-line starting current of 90 A. With an auto-transformer starter on the 80% tap, what is the line current at starting?
- (a) 72 A
- (b) 64 A
- (c) 58 A
- (d) 45 A
Answer: (c) 58 A — the line current is the tap fraction squared times the DOL current, so 0.80² × 90 = 0.64 × 90 = 57.6 A, about 58 A.
Q6. A motor has a direct-on-line starting current of 100 A. With an auto-transformer starter on the 70% tap, what is the line current at starting?
- (a) 70 A
- (b) 49 A
- (c) 35 A
- (d) 100 A
Answer: (b) 49 A — the line current is the tap fraction squared times the DOL current, so 0.70² × 100 = 0.49 × 100 = 49 A.
Q7. Compared with a star-delta starter, which gives 33% starting torque, what advantage does an auto-transformer starter offer?
- (a) It is always cheaper than star-delta
- (b) Its taps are adjustable, and a 65% tap gives about 42% starting torque — more than star-delta
- (c) It needs no contactors at all
- (d) It can vary the motor speed while running
Answer: (b) Its taps are adjustable, and a 65% tap gives about 42% starting torque — more than star-delta — so it can start loads that star-delta cannot.
Q8. At a 40% tap, the starting torque of a motor on an auto-transformer starter is:
- (a) 40% of the DOL starting torque
- (b) 16% of the DOL starting torque
- (c) 60% of the DOL starting torque
- (d) 20% of the DOL starting torque
Answer: (b) 16% of the DOL starting torque — torque varies with voltage squared, so 0.40² = 0.16, or 16%.
Q9. What happens to the auto-transformer once the motor is up to speed?
- (a) It stays in circuit for the whole run
- (b) It is switched out (bypassed) and the motor is connected direct to the supply
- (c) It is reconnected on a lower tap
- (d) It becomes the motor’s overload relay
Answer: (b) It is switched out (bypassed) and the motor is connected direct to the supply — the transformer is a starting device only.
Q10. Which load suits an auto-transformer starter best?
- (a) A small fan that starts unloaded
- (b) A large motor that needs fairly high starting torque, such as a crusher or mill, where star-delta torque is too low
- (c) A motor whose speed must vary all day
- (d) A single-phase domestic pump
Answer: (b) A large motor that needs fairly high starting torque, such as a crusher or mill, where star-delta torque is too low — the higher taps give more torque than star-delta can.
Also read: VFD vs Soft Starter | All MCQ Topics