Motor Starter MCQs — Set 3
10 practice questions on the star-delta starter — how the star connection cuts voltage and current, the changeover timer and its limits — with answers and explanations.
Q1. How many contactors does a star-delta starter use, and what are they?
- (a) One contactor only
- (b) Two: main and delta
- (c) Three: main, star and delta
- (d) Four: main, star, delta and bypass
Answer: (c) Three: main, star and delta — the main contactor stays closed throughout, while the star contactor closes at starting and the delta contactor takes over at changeover.
Q2. When the motor is connected in star, the voltage across each winding is:
- (a) The full line voltage
- (b) The line voltage ÷ √3
- (c) The line voltage × √3
- (d) Half the line voltage
Answer: (b) The line voltage ÷ √3 — in star each winding sits between a line and the star point, so it sees only 1 ÷ √3 (about 58%) of the line voltage.
Q3. A 400 V motor is started in star. What voltage appears across each winding?
- (a) 400 V
- (b) 231 V
- (c) 690 V
- (d) 133 V
Answer: (b) 231 V — star voltage = line voltage ÷ √3 = 400 ÷ 1.732 = 231 V.
Q4. In star, the starting line current is what fraction of the starting current the same motor would draw in delta?
- (a) The same
- (b) One half
- (c) One third
- (d) Three times
Answer: (c) One third — the lower winding voltage cuts the winding current, and the star connection draws still less from the line, so the line current is 1/3 of the delta starting current.
Q5. When does the timer change the motor from star to delta?
- (a) The instant the start button is pressed
- (b) After the motor has run up to about 80% of full speed, typically after a few seconds
- (c) Only when the motor is fully loaded
- (d) When the overload relay trips
Answer: (b) After the motor has run up to about 80% of full speed, typically after a few seconds — switching too early throws away the benefit of the star start.
Q6. For a star-delta starter, the motor must have:
- (a) Three terminals only
- (b) Six terminals brought out, with windings rated for delta at line voltage
- (c) Slip rings and brushes
- (d) A commutator and carbon brushes
Answer: (b) Six terminals brought out, with windings rated for delta at line voltage — the starter must be able to reconnect the same windings from star into delta.
Q7. Why is a star-delta starter unsuitable for a motor that must start under full load?
- (a) The star starting torque is only one third of the delta starting torque, so the motor may stall
- (b) The starter cannot switch the motor to delta at all under load
- (c) The timer burns out under full load
- (d) The motor draws more current in star than in delta
Answer: (a) The star starting torque is only one third of the delta starting torque, so the motor may stall — star-delta suits fans, pumps and machines that start unloaded.
Q8. What happens if the changeover to delta happens too early, before the motor has run up?
- (a) Nothing — the motor simply runs slower
- (b) A current surge almost as high as a direct-on-line start
- (c) The motor reverses direction
- (d) The star contactor stays closed forever
Answer: (b) A current surge almost as high as a direct-on-line start — the motor is still near standstill, so connecting it in delta draws nearly the full DOL current.
Q9. A 415 V motor is started in star. What voltage appears across each winding?
- (a) 415 V
- (b) 240 V
- (c) 208 V
- (d) 719 V
Answer: (b) 240 V — star voltage = line voltage ÷ √3 = 415 ÷ 1.732 = 240 V.
Q10. In an open-transition star-delta starter, what happens at changeover?
- (a) The motor stays connected to the supply the whole time
- (b) The motor is briefly disconnected from the supply, causing a current transient when delta reconnects
- (c) The motor is short-circuited for a few milliseconds
- (d) The supply frequency is doubled
Answer: (b) The motor is briefly disconnected from the supply, causing a current transient when delta reconnects — closed-transition starters avoid this with resistors, but cost more.
Also read: Power Loss Formula | All MCQ Topics