Motor Starter MCQs — Set 1

10 practice questions on why induction motors need starters — starting current, back EMF, voltage dip and heating — with answers and explanations.

Q1. Why does a three-phase induction motor draw a very high current at the instant it is switched on?

  • (a) The rotor is already turning at full speed
  • (b) There is no back EMF at standstill, so only the winding resistance and leakage reactance limit the current
  • (c) The supply voltage doubles at the moment of switching
  • (d) The motor draws its normal full-load current plus the load current

Answer: (b) There is no back EMF at standstill, so only the winding resistance and leakage reactance limit the current — at standstill the motor looks almost like a short circuit to the supply.

Q2. A motor has a full-load current of 10 A. About how much current will it draw if started direct-on-line?

  • (a) 10 A
  • (b) 30 A
  • (c) 60 A
  • (d) 120 A

Answer: (c) 60 A — a direct-on-line start draws about 6 × full-load current, so 6 × 10 = 60 A.

Q3. What effect can the direct-on-line starting of a large motor have on other equipment on the same supply?

  • (a) A voltage dip that makes lights dim or flicker and can trip other equipment
  • (b) A rise in supply frequency
  • (c) A permanent increase in supply voltage
  • (d) No effect at all on other equipment

Answer: (a) A voltage dip that makes lights dim or flicker and can trip other equipment — the heavy starting current pulls the supply voltage down for a second or two.

Q4. At the instant of switching on, before the rotor starts turning, the back EMF of an induction motor is:

  • (a) Maximum
  • (b) Zero
  • (c) Equal to the supply voltage
  • (d) Negative

Answer: (b) Zero — back EMF is produced by rotation, so at standstill there is none and the starting current is very high.

Q5. A motor with a full-load current of 15 A is started direct-on-line. About what is its starting current?

  • (a) 45 A
  • (b) 90 A
  • (c) 150 A
  • (d) 15 A

Answer: (b) 90 A — starting current is about 6 × full-load current, so 6 × 15 = 90 A.

Q6. Which of these motors most needs a starter?

  • (a) A small single-phase fan motor
  • (b) A large three-phase induction motor
  • (c) A small DC toy motor
  • (d) A synchronous clock motor

Answer: (b) A large three-phase induction motor — its starting current is many times its running current, so it needs a device to control the start.

Q7. What is meant by the locked-rotor current of a motor?

  • (a) The current drawn when the motor runs at full load
  • (b) The current drawn at standstill with the rotor prevented from turning
  • (c) The current drawn when the motor is switched off
  • (d) The current in the rotor bars only

Answer: (b) The current drawn at standstill with the rotor prevented from turning — it is the same heavy current the motor draws at the instant of starting.

Q8. A motor with a full-load current of 8 A is started direct-on-line. About what is its starting current?

  • (a) 16 A
  • (b) 24 A
  • (c) 48 A
  • (d) 80 A

Answer: (c) 48 A — starting current is about 6 × full-load current, so 6 × 8 = 48 A.

Q9. Why can repeated direct-on-line starts damage a motor?

  • (a) The high starting current causes heavy I²R heating in the windings, which overheats the insulation
  • (b) The motor runs backwards on every second start
  • (c) The supply frequency rises with each start
  • (d) The rotor bars become magnetised

Answer: (a) The high starting current causes heavy I²R heating in the windings, which overheats the insulation — that is why motors have a limit on starts per hour.

Q10. A single-phase 5 kW motor runs on 230 V at 0.9 power factor. What is its full-load current, and about how much will it draw on a direct-on-line start?

  • (a) 24.2 A full load, about 145 A at starting
  • (b) 21.7 A full load, about 130 A at starting
  • (c) 24.2 A full load, about 48 A at starting
  • (d) 12.1 A full load, about 72 A at starting

Answer: (a) 24.2 A full load, about 145 A at starting — FLC = 5000 ÷ (230 × 0.9) = 24.2 A, and a DOL start draws about 6 × 24.2 = 145 A.

Also read: VFD vs Soft Starter | All MCQ Topics