Electrical Maintenance MCQs — Set 3

10 practice questions on thermography and infrared scanning — finding hot spots before they cause a failure — with answers and explanations.

Q1. What does a thermal (infrared) camera detect during an electrical inspection?

  • (a) The voltage at each terminal
  • (b) The heat radiated by equipment, shown as a temperature image
  • (c) The insulation resistance of cables
  • (d) The sound of arcing inside a panel

Answer: (b) The heat radiated by equipment, shown as a temperature image — an infrared camera sees heat, so a loose or overloaded connection appears as a bright hot spot.

Q2. A loose terminal connection in a panel usually shows up on a thermal scan as what?

  • (a) A cold spot, colder than the rest of the panel
  • (b) A hot spot, hotter than the same connection on other phases
  • (c) No change in temperature at all
  • (d) A blue patch with no temperature meaning

Answer: (b) A hot spot, hotter than the same connection on other phases — a loose connection has higher resistance, so it heats up when current flows through it.

Q3. Why should a thermal scan of a panel be done while the equipment is under load?

  • (a) Because the camera only works when the load is on
  • (b) Because heat from a loose or overloaded connection only appears when current is flowing
  • (c) Because the panel door must be open
  • (d) Because the scan is faster under load

Answer: (b) Because heat from a loose or overloaded connection only appears when current is flowing — with no load there is no heating to see, so a faulty connection can look normal.

Q4. The temperature rise limit for a busbar connection is commonly 65 K, and the ambient temperature is 40 °C. What is the maximum allowed temperature of the connection?

  • (a) 65 °C
  • (b) 40 °C
  • (c) 105 °C
  • (d) 25 °C

Answer: (c) 105 °C — maximum temperature = ambient + rise = 40 + 65 = 105 °C, a typical limit for busbar connections.

Q5. What is emissivity in thermography?

  • (a) The voltage rating of the camera
  • (b) How well a surface gives off infrared radiation, which affects how accurate the temperature reading is
  • (c) The speed at which the camera takes pictures
  • (d) The distance the camera must be from the panel

Answer: (b) How well a surface gives off infrared radiation, which affects how accurate the temperature reading is — shiny bare metal has low emissivity and can read cooler than it really is, so readings need care.

Q6. On a thermal scan of a three-phase panel, one phase terminal is much hotter than the other two. What does this most likely indicate?

  • (a) The panel is working perfectly
  • (b) An unbalanced load or a loose connection on that phase
  • (c) The camera battery is low
  • (d) The other two phases are overloaded

Answer: (b) An unbalanced load or a loose connection on that phase — comparing similar parts under similar load is the key check in thermography, and one phase standing out means something is wrong on that phase.

Q7. How often is a thermal survey of an electrical installation commonly recommended?

  • (a) Only after a fire has happened
  • (b) At regular planned intervals, commonly once a year
  • (c) Once in the lifetime of the installation
  • (d) Every day

Answer: (b) At regular planned intervals, commonly once a year — a periodic survey catches connections as they loosen over time, before they overheat and fail.

Q8. What is a major safety advantage of infrared scanning?

  • (a) It repairs loose connections by itself
  • (b) It is done from a distance with no contact, so the panel can stay energised
  • (c) It replaces the need for an RCD
  • (d) It switches off the supply automatically

Answer: (b) It is done from a distance with no contact, so the panel can stay energised — the inspector does not need to touch live parts, which keeps the survey safe.

Q9. A thermal scan finds a breaker terminal close to its temperature limit but not over it. What is the correct action?

  • (a) Ignore it, because it has not failed yet
  • (b) Record it, schedule a re-torque and repair soon, and monitor it
  • (c) Replace the whole panel immediately without any check
  • (d) Spray water on the terminal to cool it

Answer: (b) Record it, schedule a re-torque and repair soon, and monitor it — a connection near its limit is a warning; planned repair now is far cheaper than a failure later.

Q10. Which of these faults is most likely to cause a hot spot on a breaker terminal?

  • (a) A loose terminal screw or poor contact
  • (b) A clean, dry panel interior
  • (c) A correctly sized cable
  • (d) A breaker that is switched off

Answer: (a) A loose terminal screw or poor contact — poor contact raises resistance at that point, and the lost energy appears as heat exactly at the terminal.

Also read: Surface Conduit Wiring | All MCQ Topics