Harmonics MCQs — Set 10

10 mixed revision questions on harmonics — frequencies, neutral current, troubleshooting and choosing the right mitigation for a real installation.

Q1. Each phase carries a 3rd-harmonic current of 20 A. What is the neutral current from the 3rd harmonic?

  • (a) 20 A
  • (b) 40 A
  • (c) 60 A
  • (d) 80 A

Answer: (c) 60 A — triplen currents add in the neutral: 3 × 20 A = 60 A.

Q2. On a 60 Hz supply, what is the frequency of the 5th harmonic?

  • (a) 180 Hz
  • (b) 240 Hz
  • (c) 300 Hz
  • (d) 360 Hz

Answer: (c) 300 Hz — 5 × 60 Hz = 300 Hz.

Q3. A neutral conductor overheats in a balanced three-phase office building full of computers. What is the most likely cause?

  • (a) Triplen harmonics from the single-phase SMPS loads adding in the neutral
  • (b) An unbalanced load on one phase
  • (c) The fundamental currents adding in the neutral
  • (d) The neutral being too large for the load

Answer: (a) Triplen harmonics from the single-phase SMPS loads adding in the neutral — in a balanced system the fundamental currents cancel in the neutral, but triplen harmonics do not.

Q4. On a 50 Hz supply, what is the frequency of the 11th harmonic?

  • (a) 450 Hz
  • (b) 500 Hz
  • (c) 550 Hz
  • (d) 600 Hz

Answer: (c) 550 Hz — 11 × 50 Hz = 550 Hz.

Q5. A plant has high 5th and 7th harmonic currents from several 6-pulse VFDs. Which single change gives the biggest reduction at the source?

  • (a) Replacing the 6-pulse drives with 12-pulse drives or adding a harmonic filter
  • (b) Fitting a larger standard transformer
  • (c) Adding more resistive heaters
  • (d) Reducing the supply voltage

Answer: (a) Replacing the 6-pulse drives with 12-pulse drives or adding a harmonic filter — both attack the 5th and 7th harmonics at their source instead of merely tolerating them.

Q6. In a balanced three-phase system, each phase carries 12 A of 3rd-harmonic current. What current flows in the neutral from the 3rd harmonic?

  • (a) 12 A
  • (b) 36 A
  • (c) 0 A
  • (d) 24 A

Answer: (b) 36 A — 3rd harmonics are triplen, so they add in the neutral instead of cancelling: 3 × 12 = 36 A.

Q7. On a 50 Hz supply, what is the frequency of the 13th harmonic?

  • (a) 550 Hz
  • (b) 600 Hz
  • (c) 650 Hz
  • (d) 700 Hz

Answer: (c) 650 Hz — 13 × 50 Hz = 650 Hz.

Q8. A sensitive electronic instrument malfunctions when a nearby VFD runs, but works normally when the VFD is off. What is the most likely cause?

  • (a) Harmonic voltage distortion and electrical noise from the VFD affecting the instrument
  • (b) The instrument drawing too much fundamental current
  • (c) The supply frequency dropping to zero
  • (d) The instrument being connected to the wrong phase

Answer: (a) Harmonic voltage distortion and electrical noise from the VFD affecting the instrument — distorted voltage and high-frequency switching noise can upset sensitive electronics, so filtering or separation is needed.

Q9. What is the correct first step when investigating a suspected harmonic problem in a plant?

  • (a) Measure voltage and current THD and the harmonic spectrum with a power quality analyser at the PCC
  • (b) Immediately replace the main transformer
  • (c) Disconnect all loads without measuring anything
  • (d) Fit the largest capacitor bank available

Answer: (a) Measure voltage and current THD and the harmonic spectrum with a power quality analyser at the PCC — measurement identifies which harmonics dominate and where they come from before any money is spent on a fix.

Q10. A building has a high neutral current, overheating transformers and nuisance tripping. Which combined fix addresses all three symptoms?

  • (a) A K-rated transformer, an oversized neutral and harmonic filtering at the main harmonic sources
  • (b) A smaller transformer and thinner neutral cable
  • (c) Removing all circuit breakers
  • (d) Adding an undetuned capacitor bank with no reactor

Answer: (a) A K-rated transformer, an oversized neutral and harmonic filtering at the main harmonic sources — the filter cuts the harmonics, the K-rated transformer tolerates what remains, and the larger neutral carries the triplen current safely.