Harmonics MCQs — Set 9
10 practice questions on harmonic standards, power factor and resonance — IEEE 519 limits, true power factor and what happens when capacitors resonate.
Q1. Which standard is most widely used to set limits on harmonic distortion in power systems?
- (a) IEEE 519
- (b) Ohm’s law
- (c) Faraday’s law
- (d) Kirchhoff’s current law
Answer: (a) IEEE 519 — it sets recommended limits for voltage and current harmonic distortion at the point of common coupling.
Q2. Under IEEE 519, what does the allowed current distortion depend on?
- (a) The ratio of short-circuit current to maximum load current (Isc ÷ IL) at the PCC
- (b) The colour of the cable insulation
- (c) The age of the transformer only
- (d) The number of light fittings in the building
Answer: (a) The ratio of short-circuit current to maximum load current (Isc ÷ IL) at the PCC — a stiff supply (high Isc ÷ IL) can tolerate more harmonic current than a weak one.
Q3. How does harmonic distortion affect the true power factor?
- (a) True power factor = displacement power factor × distortion power factor, so harmonics lower it
- (b) Harmonics always raise the true power factor to unity
- (c) Harmonics have no effect on power factor
- (d) True power factor depends only on the load resistance
Answer: (a) True power factor = displacement power factor × distortion power factor, so harmonics lower it — the distortion factor is below 1 whenever THD is present, pulling the true power factor down.
Q4. What is total harmonic distortion (THD)?
- (a) The ratio of the RMS value of all harmonic components to the RMS value of the fundamental
- (b) The ratio of peak current to RMS current
- (c) The frequency of the highest harmonic present
- (d) The phase angle between voltage and current
Answer: (a) The ratio of the RMS value of all harmonic components to the RMS value of the fundamental — THD compares all the harmonic content with the fundamental, and is usually given as a percentage.
Q5. What is resonance in a system containing inductance and a capacitor bank?
- (a) The condition where inductive reactance equals capacitive reactance at a particular frequency
- (b) The condition where the capacitor bank is fully discharged
- (c) The condition where current stops flowing completely
- (d) The condition where the supply frequency becomes zero
Answer: (a) The condition where inductive reactance equals capacitive reactance at a particular frequency — at that frequency the circuit offers very low (series) or very high (parallel) impedance.
Q6. What happens during parallel resonance at a harmonic frequency?
- (a) Harmonic voltage and current are amplified, which can overload capacitors and transformers
- (b) All harmonics disappear completely
- (c) The supply voltage becomes a pure sine wave
- (d) The capacitor bank stops drawing any current
Answer: (a) Harmonic voltage and current are amplified, which can overload capacitors and transformers — parallel resonance presents a high impedance, so a small harmonic current produces a large harmonic voltage.
Q7. What happens during series resonance at a harmonic frequency?
- (a) The circuit offers very low impedance, so a large harmonic current can flow
- (b) The circuit offers infinite impedance and blocks all current
- (c) The harmonic is converted to the fundamental
- (d) The voltage across the capacitor falls to zero
Answer: (a) The circuit offers very low impedance, so a large harmonic current can flow — at series resonance the inductive and capacitive reactances cancel, leaving only the small resistance.
Q8. For systems below 69 kV, what total voltage distortion (THDv) limit does IEEE 519 recommend?
- (a) 5%
- (b) 15%
- (c) 25%
- (d) 50%
Answer: (a) 5% — IEEE 519 recommends a maximum voltage THD of 5% for systems below 69 kV, with no individual harmonic above 3%.
Q9. For systems below 69 kV, what is the IEEE 519 limit for any single individual voltage harmonic?
- (a) 1%
- (b) 3%
- (c) 8%
- (d) 10%
Answer: (b) 3% — no individual voltage harmonic should exceed 3% of the fundamental voltage in systems below 69 kV.
Q10. A capacitor bank installed for power-factor correction starts overheating after new VFDs are added. What is the most likely explanation?
- (a) The system is resonating near a harmonic produced by the VFDs, amplifying harmonic current into the capacitors
- (b) The capacitors are now too small to correct the power factor
- (c) The VFDs have removed all harmonics from the system
- (d) The capacitor bank is drawing only fundamental current
Answer: (a) The system is resonating near a harmonic produced by the VFDs, amplifying harmonic current into the capacitors — the transformer inductance and the capacitor bank can resonate at a harmonic frequency, and detuned reactors are the usual fix.
Also read: Power Loss Formula | All MCQ Topics