Fuse MCQs — Set 7
10 practice questions on I²t let-through energy — calculating the energy a fuse passes during a fault — with worked answers.
Q1. The I²t value of a fuse represents…
- (a) the energy let through during fault clearance
- (b) the rated voltage
- (c) the fusing factor
- (d) the power consumed by the fuse
Answer: (a) the energy let through during fault clearance — I²t is the heating energy passed to the circuit before the fuse clears the fault.
Q2. A fault current of 100 A flows for 0.01 s before the fuse clears it. What is the I²t let-through?
- (a) 10 A²s
- (b) 100 A²s
- (c) 1,000 A²s
- (d) 1 A²s
Answer: (b) 100 A²s — I²t = 100² × 0.01 = 10,000 × 0.01 = 100 A²s.
Q3. A fault current of 50 A flows for 0.02 s. What is the I²t?
- (a) 25 A²s
- (b) 50 A²s
- (c) 100 A²s
- (d) 5 A²s
Answer: (b) 50 A²s — I²t = 50² × 0.02 = 2,500 × 0.02 = 50 A²s.
Q4. A fault current of 200 A flows for 0.005 s. What is the I²t?
- (a) 100 A²s
- (b) 200 A²s
- (c) 400 A²s
- (d) 20 A²s
Answer: (b) 200 A²s — I²t = 200² × 0.005 = 40,000 × 0.005 = 200 A²s.
Q5. A fault current of 10 A flows for 0.1 s. What is the I²t?
- (a) 1 A²s
- (b) 10 A²s
- (c) 100 A²s
- (d) 0.1 A²s
Answer: (b) 10 A²s — I²t = 10² × 0.1 = 100 × 0.1 = 10 A²s.
Q6. A fault current of 1,000 A flows for 0.001 s. What is the I²t?
- (a) 100 A²s
- (b) 1,000 A²s
- (c) 10,000 A²s
- (d) 10 A²s
Answer: (b) 1,000 A²s — I²t = 1,000² × 0.001 = 1,000,000 × 0.001 = 1,000 A²s.
Q7. A fault current of 20 A flows for 0.05 s. What is the I²t?
- (a) 2 A²s
- (b) 20 A²s
- (c) 200 A²s
- (d) 100 A²s
Answer: (b) 20 A²s — I²t = 20² × 0.05 = 400 × 0.05 = 20 A²s.
Q8. A fault current of 150 A flows for 0.02 s. What is the I²t?
- (a) 225 A²s
- (b) 450 A²s
- (c) 900 A²s
- (d) 45 A²s
Answer: (b) 450 A²s — I²t = 150² × 0.02 = 22,500 × 0.02 = 450 A²s.
Q9. A fault current of 80 A flows for 0.01 s. What is the I²t?
- (a) 8 A²s
- (b) 64 A²s
- (c) 640 A²s
- (d) 16 A²s
Answer: (b) 64 A²s — I²t = 80² × 0.01 = 6,400 × 0.01 = 64 A²s.
Q10. Why is a low I²t value desirable in a fuse?
- (a) It lets the fuse carry more load
- (b) It lets less energy through to the protected equipment
- (c) It raises the fusing factor
- (d) It increases the operating time
Answer: (b) It lets less energy through to the protected equipment — less let-through energy means less heating and damage during a fault.