EV Charging MCQs — Set 7
10 practice questions on home charger installation — circuit sizing, breaker selection and cable size.
Q1. A 7 kW single-phase home charger runs on 230 V. What current does it draw?
- (a) 15.7 A
- (b) 24.2 A
- (c) 30.4 A
- (d) 47.8 A
Answer: (c) 30.4 A — I = P ÷ V = 7,000 W ÷ 230 V = 30.4 A, so a 32 A breaker with 6 mm² cable is the usual choice.
Q2. A 3.6 kW charger runs on 230 V. What current does it draw, and which breaker fits?
- (a) 10 A — 10 A breaker
- (b) 15.7 A — 16 A breaker
- (c) 20 A — 20 A breaker
- (d) 30.4 A — 32 A breaker
Answer: (b) 15.7 A — 16 A breaker — I = 3,600 ÷ 230 = 15.65 A, about 15.7 A, so a 16 A breaker is the correct size.
Q3. An 11 kW three-phase charger runs on 400 V. What current does it draw per phase?
- (a) 27.5 A
- (b) 15.9 A
- (c) 47.8 A
- (d) 11.0 A
Answer: (b) 15.9 A — I = P ÷ (√3 × V) = 11,000 ÷ (1.732 × 400) = 11,000 ÷ 692.8 = 15.9 A.
Q4. A 22 kW three-phase charger runs on 400 V. What current does it draw per phase?
- (a) 15.9 A
- (b) 22.0 A
- (c) 31.8 A
- (d) 55.0 A
Answer: (c) 31.8 A — I = 22,000 ÷ (1.732 × 400) = 22,000 ÷ 692.8 = 31.75 A, about 31.8 A, so a 32 A breaker fits.
Q5. A 7.4 kW single-phase charger runs on 230 V. What current does it draw?
- (a) 30.4 A
- (b) 32.2 A
- (c) 16.0 A
- (d) 24.2 A
Answer: (b) 32.2 A — I = 7,400 ÷ 230 = 32.17 A, about 32.2 A, so a 40 A breaker is needed (a 32 A breaker would be too small).
Q6. Under the NEC 80% continuous-load rule, what is the maximum safe charging power on a 20 A, 120 V circuit?
- (a) 2,400 W
- (b) 1,920 W
- (c) 1,440 W
- (d) 3,000 W
Answer: (b) 1,920 W — continuous loads are limited to 80% of the breaker rating: 20 A × 120 V × 0.8 = 1,920 W.
Q7. Why must a home EV charger be installed on its own dedicated circuit?
- (a) To make charging faster
- (b) Because it draws high current for hours, and sharing the circuit risks overloading the wiring and breaker
- (c) Because the charger needs a different voltage
- (d) To avoid paying for electricity
Answer: (b) Because it draws high current for hours, and sharing the circuit risks overloading the wiring and breaker — a dedicated circuit keeps the sustained load off circuits that serve other appliances.
Q8. A 2.3 kW charger runs on 230 V. What current does it draw?
- (a) 5 A
- (b) 10 A
- (c) 15.7 A
- (d) 20 A
Answer: (b) 10 A — I = 2,300 ÷ 230 = 10 A, which is why a standard 13 A plug can supply a 2.3 kW (granny) charger.
Q9. An 11 kW single-phase charger runs on 230 V. What current does it draw?
- (a) 30.4 A
- (b) 15.9 A
- (c) 47.8 A
- (d) 32.2 A
Answer: (c) 47.8 A — I = 11,000 ÷ 230 = 47.83 A, about 47.8 A, which is why 11 kW single-phase charging needs a very large supply and is usually done three-phase instead.
Q10. A 5 kW charger runs on 230 V at a power factor of 0.9. What current does it draw?
- (a) 21.7 A
- (b) 24.2 A
- (c) 30.4 A
- (d) 19.6 A
Answer: (b) 24.2 A — I = P ÷ (V × pf) = 5,000 ÷ (230 × 0.9) = 5,000 ÷ 207 = 24.15 A, about 24.2 A.