Distribution Board MCQs — Set 9

10 practice questions on sizing a distribution board and leaving room for future circuits, with worked answers.

Q1. How many outgoing circuit positions does a 12-way distribution board have?

  • (a) 6
  • (b) 12
  • (c) 24
  • (d) 100

Answer: (b) 12 — the number of ways is the number of outgoing MCB positions the board provides.

Q2. Why should spare ways be left in a distribution board?

  • (a) To make the board cheaper
  • (b) So future circuits can be added without replacing the whole board
  • (c) To reduce the supply voltage
  • (d) To increase the IP rating

Answer: (b) So future circuits can be added without replacing the whole board — a new air conditioner, socket or EV charger can be wired into a spare way later.

Q3. A home needs 9 circuits now. Which distribution board is the sensible choice?

  • (a) A 6-way board
  • (b) A 9-way board with no spares
  • (c) A 12-way board, leaving 3 spare ways
  • (d) A board with no main switch

Answer: (c) A 12-way board, leaving 3 spare ways — choosing a board one or two sizes larger than today’s need leaves room for future circuits.

Q4. What is the job of the main switch (incomer) in a distribution board?

  • (a) To protect each final circuit separately
  • (b) To isolate the whole board from the supply
  • (c) To measure the energy used
  • (d) To step the voltage down

Answer: (b) To isolate the whole board from the supply — the main switch isolates the entire board; the individual MCBs protect the separate final circuits.

Q5. Under the NEC 80% rule, what is the maximum continuous load on a 15 A, 120 V breaker?

  • (a) 1,800 W
  • (b) 1,440 W
  • (c) 1,200 W
  • (d) 960 W

Answer: (b) 1,440 W — 15 × 120 × 0.8 = 1,440 W (12 A continuous).

Q6. A 2 kW heater runs from a 230 V circuit in the board. What current does it draw?

  • (a) 4.35 A
  • (b) 8.7 A
  • (c) 13.0 A
  • (d) 2.0 A

Answer: (b) 8.7 A — I = P ÷ V = 2,000 ÷ 230 = 8.7 A.

Q7. A 3 kW water heater runs from a 230 V circuit in the board. What current does it draw?

  • (a) 6.5 A
  • (b) 10.4 A
  • (c) 13.0 A
  • (d) 30.0 A

Answer: (c) 13.0 A — I = P ÷ V = 3,000 ÷ 230 = 13.0 A.

Q8. What happens if a distribution board is undersized for the installation?

  • (a) There is no room for new circuits and the board may be overloaded
  • (b) The supply voltage rises
  • (c) The MCBs trip faster
  • (d) The board becomes waterproof

Answer: (a) There is no room for new circuits and the board may be overloaded — an undersized board forces double-ups on ways and leaves no spare capacity for growth.

Q9. How is the total load on a distribution board checked against its incomer rating?

  • (a) By adding up the ratings of every MCB in the board
  • (b) By summing the circuit demands after applying diversity and comparing with the main switch rating
  • (c) By counting the number of ways
  • (d) By measuring the board’s weight

Answer: (b) By summing the circuit demands after applying diversity and comparing with the main switch rating — simply adding MCB ratings overstates the load, since not all circuits run at full load together.

Q10. Cables feeding a sub-distribution board run through conduit. What is the maximum permitted conduit fill?

  • (a) 100%
  • (b) 80%
  • (c) 40%
  • (d) 10%

Answer: (c) 40% — cables must not fill more than 40% of a conduit’s cross-section, leaving room for heat to escape and for cables to be pulled in or replaced.

Also read: Surface Conduit Wiring | All MCQ Topics