Distribution Board MCQs — Set 7
10 practice questions on diversity and maximum demand for sizing a distribution board, with worked answers.
Q1. A house has 10 kW of connected load and a diversity factor of 60% is applied. What is the maximum demand?
- (a) 16 kW
- (b) 6 kW
- (c) 4 kW
- (d) 10 kW
Answer: (b) 6 kW — maximum demand = connected load × diversity factor = 10 × 0.60 = 6 kW.
Q2. A small workshop has 20 kW of connected load with a diversity factor of 50%. What is the maximum demand?
- (a) 10 kW
- (b) 40 kW
- (c) 5 kW
- (d) 15 kW
Answer: (a) 10 kW — maximum demand = 20 × 0.50 = 10 kW.
Q3. Lighting load of 8 kW is assessed with a diversity factor of 66%. What is the lighting demand?
- (a) 12.1 kW
- (b) 2.7 kW
- (c) 5.3 kW
- (d) 8 kW
Answer: (c) 5.3 kW — demand = 8 × 0.66 = 5.28 kW, about 5.3 kW.
Q4. A shop has 12 kW of connected load and a diversity factor of 75% is applied. What is the maximum demand?
- (a) 16 kW
- (b) 3 kW
- (c) 9 kW
- (d) 12 kW
Answer: (c) 9 kW — maximum demand = 12 × 0.75 = 9 kW.
Q5. An office has 15 kW of connected load with a diversity factor of 40%. What is the maximum demand?
- (a) 6 kW
- (b) 37.5 kW
- (c) 9 kW
- (d) 15 kW
Answer: (a) 6 kW — maximum demand = 15 × 0.40 = 6 kW.
Q6. A distribution board supplies a maximum demand of 6 kW at 230 V single-phase with a power factor of 1. What is the design current?
- (a) 13.0 A
- (b) 26.1 A
- (c) 38.3 A
- (d) 6.0 A
Answer: (b) 26.1 A — I = P ÷ V = 6,000 ÷ 230 = 26.1 A.
Q7. A board supplies a 10 kW load at 230 V with a power factor of 0.9. What current does it draw?
- (a) 43.5 A
- (b) 48.3 A
- (c) 39.1 A
- (d) 23.0 A
Answer: (b) 48.3 A — I = P ÷ (V × pf) = 10,000 ÷ (230 × 0.9) = 10,000 ÷ 207 = 48.3 A.
Q8. A three-phase board supplies an 18 kW load at 400 V with a power factor of 0.9. What is the current per phase?
- (a) 45.0 A
- (b) 26.0 A
- (c) 28.9 A
- (d) 20.0 A
Answer: (c) 28.9 A — I = P ÷ (√3 × V × pf) = 18,000 ÷ (1.732 × 400 × 0.9) = 18,000 ÷ 623.5 = 28.9 A.
Q9. A 5 kW load at 230 V with a power factor of 0.9 draws 24.2 A. With a 25% design margin the current is 30.2 A. What cable size is suitable?
- (a) 1.5 mm²
- (b) 2.5 mm²
- (c) 4 mm²
- (d) 1 mm²
Answer: (c) 4 mm² — I = 5,000 ÷ (230 × 0.9) = 24.2 A, and 24.2 × 1.25 = 30.2 A, so a 4 mm² cable (rated above 30 A) is the correct choice.
Q10. What is a diversity factor in distribution board design?
- (a) The ratio of maximum demand to total connected load
- (b) The number of phases in the board
- (c) The ratio of voltage to current
- (d) The number of spare ways in the board
Answer: (a) The ratio of maximum demand to total connected load — because not every appliance runs at once, the board is sized for the realistic maximum demand rather than the sum of every load.
Also read: Cable Sizing MCQs | All MCQ Topics