Contactor MCQs — Set 8
10 practice questions on start–stop control — the seal-in holding circuit, jog control and emergency stop — with answers and explanations.
Q1. How is the seal-in (holding) contact wired in a start–stop circuit?
- (a) In series with the stop button
- (b) In parallel with the start push button
- (c) Across the overload relay heater
- (d) In series with the motor
Answer: (b) In parallel with the start push button — when the contactor picks up, this NO auxiliary contact closes and keeps the coil energised after the button is released.
Q2. In a start–stop station, the STOP push button contact is of which type?
- (a) Normally open (NO)
- (b) Normally closed (NC)
- (c) Changeover only
- (d) Timed
Answer: (b) Normally closed (NC) — pressing STOP opens the coil circuit and drops the contactor out.
Q3. In a start–stop station, the START push button contact is of which type?
- (a) Normally closed (NC)
- (b) Normally open (NO)
- (c) Earthed
- (d) Timed
Answer: (b) Normally open (NO) — pressing START closes the contact and energises the coil.
Q4. What happens when the START button is released in a circuit with a holding contact?
- (a) The contactor drops out and the motor stops
- (b) The NO auxiliary contact keeps the coil energised, so the motor keeps running
- (c) The overload relay trips
- (d) The coil burns out
Answer: (b) The NO auxiliary contact keeps the coil energised, so the motor keeps running — the seal-in contact has taken over from the start button.
Q5. What happens when the STOP button is pressed?
- (a) The coil circuit is completed and the motor starts
- (b) The coil circuit is broken, the contactor drops out and the seal-in contact opens
- (c) The motor reverses
- (d) The coil voltage doubles
Answer: (b) The coil circuit is broken, the contactor drops out and the seal-in contact opens — the motor stops and stays stopped until START is pressed again.
Q6. After a supply failure and restoration, what does a motor with a holding circuit do?
- (a) It restarts automatically
- (b) It stays off until the START button is pressed again
- (c) It runs in reverse
- (d) It trips the circuit breaker
Answer: (b) It stays off until the START button is pressed again — this is no-voltage protection, and it prevents a dangerous unexpected restart.
Q7. Two START buttons at different places for the same motor are wired how?
- (a) In series with each other
- (b) In parallel with each other
- (c) One in series and one in parallel
- (d) Across the main contacts
Answer: (b) In parallel with each other — pressing either START button completes the coil circuit.
Q8. Two STOP buttons at different places for the same motor are wired how?
- (a) In parallel with each other
- (b) In series with each other
- (c) Across the coil
- (d) In parallel with the motor
Answer: (b) In series with each other — pressing either STOP button breaks the coil circuit, since both NC contacts are in the same series path.
Q9. How does a jog (inching) circuit differ from a normal holding circuit?
- (a) Jog uses a larger contactor
- (b) Jog has no seal-in contact, so the motor runs only while the button is held down
- (c) Jog uses an NC start button
- (d) Jog needs no stop button
Answer: (b) Jog has no seal-in contact, so the motor runs only while the button is held down — releasing the button drops the contactor out at once.
Q10. How is an emergency stop button wired in a contactor control circuit?
- (a) In parallel with the start button, as an NO contact
- (b) In series with the contactor coil, as a latching NC contact
- (c) Across the main contacts
- (d) In the earth wire
Answer: (b) In series with the contactor coil, as a latching NC contact — pressing it breaks the coil circuit and it stays open until deliberately reset.