Contactor MCQs — Set 8

10 practice questions on start–stop control — the seal-in holding circuit, jog control and emergency stop — with answers and explanations.

Q1. How is the seal-in (holding) contact wired in a start–stop circuit?

  • (a) In series with the stop button
  • (b) In parallel with the start push button
  • (c) Across the overload relay heater
  • (d) In series with the motor

Answer: (b) In parallel with the start push button — when the contactor picks up, this NO auxiliary contact closes and keeps the coil energised after the button is released.

Q2. In a start–stop station, the STOP push button contact is of which type?

  • (a) Normally open (NO)
  • (b) Normally closed (NC)
  • (c) Changeover only
  • (d) Timed

Answer: (b) Normally closed (NC) — pressing STOP opens the coil circuit and drops the contactor out.

Q3. In a start–stop station, the START push button contact is of which type?

  • (a) Normally closed (NC)
  • (b) Normally open (NO)
  • (c) Earthed
  • (d) Timed

Answer: (b) Normally open (NO) — pressing START closes the contact and energises the coil.

Q4. What happens when the START button is released in a circuit with a holding contact?

  • (a) The contactor drops out and the motor stops
  • (b) The NO auxiliary contact keeps the coil energised, so the motor keeps running
  • (c) The overload relay trips
  • (d) The coil burns out

Answer: (b) The NO auxiliary contact keeps the coil energised, so the motor keeps running — the seal-in contact has taken over from the start button.

Q5. What happens when the STOP button is pressed?

  • (a) The coil circuit is completed and the motor starts
  • (b) The coil circuit is broken, the contactor drops out and the seal-in contact opens
  • (c) The motor reverses
  • (d) The coil voltage doubles

Answer: (b) The coil circuit is broken, the contactor drops out and the seal-in contact opens — the motor stops and stays stopped until START is pressed again.

Q6. After a supply failure and restoration, what does a motor with a holding circuit do?

  • (a) It restarts automatically
  • (b) It stays off until the START button is pressed again
  • (c) It runs in reverse
  • (d) It trips the circuit breaker

Answer: (b) It stays off until the START button is pressed again — this is no-voltage protection, and it prevents a dangerous unexpected restart.

Q7. Two START buttons at different places for the same motor are wired how?

  • (a) In series with each other
  • (b) In parallel with each other
  • (c) One in series and one in parallel
  • (d) Across the main contacts

Answer: (b) In parallel with each other — pressing either START button completes the coil circuit.

Q8. Two STOP buttons at different places for the same motor are wired how?

  • (a) In parallel with each other
  • (b) In series with each other
  • (c) Across the coil
  • (d) In parallel with the motor

Answer: (b) In series with each other — pressing either STOP button breaks the coil circuit, since both NC contacts are in the same series path.

Q9. How does a jog (inching) circuit differ from a normal holding circuit?

  • (a) Jog uses a larger contactor
  • (b) Jog has no seal-in contact, so the motor runs only while the button is held down
  • (c) Jog uses an NC start button
  • (d) Jog needs no stop button

Answer: (b) Jog has no seal-in contact, so the motor runs only while the button is held down — releasing the button drops the contactor out at once.

Q10. How is an emergency stop button wired in a contactor control circuit?

  • (a) In parallel with the start button, as an NO contact
  • (b) In series with the contactor coil, as a latching NC contact
  • (c) Across the main contacts
  • (d) In the earth wire

Answer: (b) In series with the contactor coil, as a latching NC contact — pressing it breaks the coil circuit and it stays open until deliberately reset.

Also read: GFCI Outlet Keeps Tripping | Transformer MCQs | All MCQ Topics