Contactor MCQs — Set 7
10 practice questions on reversing starters and interlocking — two contactors, phase swapping and why both must never close together — with answers and explanations.
Q1. How many contactors does a forward–reverse starter use?
- (a) 1
- (b) 2
- (c) 3
- (d) 4
Answer: (b) 2 — one contactor for forward rotation and one for reverse rotation.
Q2. What is the purpose of interlocking in a reversing starter?
- (a) To increase the motor speed
- (b) To prevent both contactors closing at the same time, which would short two phases together
- (c) To reduce the starting current
- (d) To protect against overload
Answer: (b) To prevent both contactors closing at the same time, which would short two phases together — a line-to-line short circuit would result.
Q3. How is electrical interlocking done between two contactors?
- (a) By wiring the NC auxiliary contact of each contactor into the other contactor’s coil circuit
- (b) By wiring the main contacts in parallel
- (c) By using a larger coil
- (d) By connecting both coils to the same push button
Answer: (a) By wiring the NC auxiliary contact of each contactor into the other contactor’s coil circuit — when one contactor is on, its NC contact opens and blocks the other coil.
Q4. What does a mechanical interlock do in a reversing starter?
- (a) It trips the overload relay
- (b) It physically blocks the second contactor from closing while the first is closed
- (c) It changes the coil voltage
- (d) It swaps the phases automatically
Answer: (b) It physically blocks the second contactor from closing while the first is closed — it is a backup to electrical interlocking.
Q5. How is the direction of a three-phase motor reversed?
- (a) By swapping the neutral and earth wires
- (b) By swapping any two of the three supply phases
- (c) By reversing the coil polarity
- (d) By increasing the supply frequency
Answer: (b) By swapping any two of the three supply phases — this reverses the rotating magnetic field and so the direction of rotation.
Q6. What happens if both the forward and reverse contactors close together?
- (a) The motor runs at double speed
- (b) A line-to-line short circuit occurs
- (c) The motor stops safely
- (d) The overload relay resets
Answer: (b) A line-to-line short circuit occurs — two phases are connected together through the two contactors, so a heavy fault current flows.
Q7. With electrical interlocking, what happens if the REVERSE button is pressed while the motor is running FORWARD?
- (a) The motor reverses at once
- (b) The reverse contactor stays off until the forward contactor drops out
- (c) Both contactors close together
- (d) The motor speed doubles
Answer: (b) The reverse contactor stays off until the forward contactor drops out — the forward contactor’s NC contact in the reverse coil circuit is open while it is running.
Q8. How is a limit switch wired in a forward–reverse drive, such as a crane or gate?
- (a) In parallel with the motor
- (b) In series with the coil circuit, as an NC contact that opens at the end of travel
- (c) Across the contactor coil
- (d) In the earth wire
Answer: (b) In series with the coil circuit, as an NC contact that opens at the end of travel — opening the coil circuit stops the motor at the limit.
Q9. Which auxiliary contact of the forward contactor is wired into the reverse contactor’s coil circuit?
- (a) An NO auxiliary contact
- (b) An NC auxiliary contact
- (c) A main contact
- (d) The overload relay contact
Answer: (b) An NC auxiliary contact — it is closed when forward is off (allowing reverse) and opens when forward picks up (blocking reverse).
Q10. In a reversing starter, which two phases are swapped to reverse the motor?
- (a) The neutral and one phase
- (b) Any two phases, for example L1 and L2
- (c) All three phases
- (d) The earth and one phase
Answer: (b) Any two phases, for example L1 and L2 — swapping any two phases reverses the phase sequence and the direction of rotation.
Also read: AFCI Breaker Keeps Tripping | Wiring Systems MCQs | All MCQ Topics