Contactor MCQs — Set 5
10 practice questions comparing contactors with relays, starters and circuit breakers — what each device does and does not do — with answers and explanations.
Q1. What is the main difference between a contactor and a control relay?
- (a) A relay has a coil and a contactor does not
- (b) A contactor switches high-power load currents; a relay switches only low-power signals
- (c) A relay can switch three-phase motors and a contactor cannot
- (d) A contactor works on DC only and a relay on AC only
Answer: (b) A contactor switches high-power load currents; a relay switches only low-power signals — contactors have larger contacts and arc chutes for load duty.
Q2. What does a direct-on-line (DOL) starter add to a plain contactor?
- (a) A circuit breaker only
- (b) An overload relay plus start and stop push buttons
- (c) A transformer
- (d) A second coil
Answer: (b) An overload relay plus start and stop push buttons — together they form a complete motor starter.
Q3. Which device interrupts a short-circuit fault current?
- (a) The contactor
- (b) The overload relay
- (c) The circuit breaker (MCB/MCCB)
- (d) The auxiliary contact block
Answer: (c) The circuit breaker (MCB/MCCB) — a contactor is not designed to break fault currents and would be destroyed trying.
Q4. How do contactor main contacts differ from relay contacts?
- (a) Contactor contacts are larger, heavier and fitted with arc chutes
- (b) Relay contacts are larger than contactor contacts
- (c) Contactor contacts are made of plastic
- (d) There is no physical difference
Answer: (a) Contactor contacts are larger, heavier and fitted with arc chutes — they must make and break load current many thousands of times.
Q5. Can a contactor replace an MCB in a motor circuit?
- (a) Yes, it provides the same protection
- (b) No, it provides no short-circuit or overload protection
- (c) Yes, if the coil voltage is 230 V
- (d) No, because it cannot switch three phases
Answer: (b) No, it provides no short-circuit or overload protection — an MCB or MCCB plus an overload relay are still needed.
Q6. What is a magnetic starter?
- (a) A contactor and an overload relay combined in one unit
- (b) A manual switch with a fuse
- (c) A soft starter with a thyristor
- (d) A star-delta timer
Answer: (a) A contactor and an overload relay combined in one unit — the contactor switches, the overload relay protects the motor.
Q7. What is an advantage of a solid-state contactor over an electromagnetic contactor?
- (a) It provides full galvanic isolation when off
- (b) It has no moving contacts, so there is no contact wear and switching is silent and fast
- (c) It needs no heatsink
- (d) It has no leakage current when off
Answer: (b) It has no moving contacts, so there is no contact wear and switching is silent and fast — the trade-off is leakage current and heat, so it needs a heatsink.
Q8. How does a latching (bistable) contactor stay closed after the control pulse is removed?
- (a) Its coil stays energised forever
- (b) A mechanical latch or permanent magnet holds the armature in position until a reset pulse
- (c) The return spring is removed
- (d) The overload relay holds it closed
Answer: (b) A mechanical latch or permanent magnet holds the armature in position until a reset pulse — it needs power only during the short switching pulse.
Q9. Why can a contactor not be used as the main isolator for maintenance?
- (a) It switches too slowly
- (b) It is not designed to guarantee safe isolation — contacts can weld and there is no visible break
- (c) It has no coil
- (d) It works only on single-phase supply
Answer: (b) It is not designed to guarantee safe isolation — contacts can weld and there is no visible break, so a proper isolator or disconnector must be used.
Q10. Where is the thermal overload relay connected in a starter?
- (a) In parallel with the motor
- (b) In series with the motor in the main circuit, after the contactor main contacts
- (c) Across the contactor coil
- (d) In the earth wire
Answer: (b) In series with the motor in the main circuit, after the contactor main contacts — motor current flows through its heaters, and its NC contact trips the contactor coil on overload.