Contactor MCQs — Set 2

10 practice questions on main and auxiliary contacts — NO vs NC, terminal markings and add-on blocks — with answers and explanations.

Q1. What is the difference between main contacts and auxiliary contacts?

  • (a) Main contacts are for the control circuit and auxiliary contacts for the load
  • (b) Main contacts carry the load current; auxiliary contacts carry only small control-circuit current
  • (c) Main contacts are always NC and auxiliary contacts are always NO
  • (d) There is no difference — the names are interchangeable

Answer: (b) Main contacts carry the load current; auxiliary contacts carry only small control-circuit current — auxiliaries are used for signalling, interlocking and holding circuits.

Q2. What is the state of a normally open (NO) contact when the contactor coil is de-energised?

  • (a) Closed
  • (b) Open
  • (c) Short-circuited
  • (d) Earthed

Answer: (b) Open — a NO contact closes only when the coil is energised.

Q3. What is the state of a normally closed (NC) contact when the contactor coil is energised?

  • (a) Closed
  • (b) Open
  • (c) Short-circuited
  • (d) Earthed

Answer: (b) Open — a NC contact is closed at rest and opens when the coil is energised.

Q4. On a contactor, terminals marked 13–14 indicate which type of contact?

  • (a) A normally closed auxiliary contact
  • (b) A normally open auxiliary contact
  • (c) A main contact
  • (d) The coil terminals

Answer: (b) A normally open auxiliary contact — the 13–14 numbering is the standard marking for an NO auxiliary contact.

Q5. On a contactor, terminals marked 21–22 indicate which type of contact?

  • (a) A normally open auxiliary contact
  • (b) A normally closed auxiliary contact
  • (c) A main contact
  • (d) The coil terminals

Answer: (b) A normally closed auxiliary contact — the 21–22 numbering is the standard marking for an NC auxiliary contact.

Q6. Which contact is used for the seal-in (holding) circuit of a start–stop starter?

  • (a) An NC auxiliary contact in series with the start button
  • (b) An NO auxiliary contact wired in parallel with the start push button
  • (c) A main contact in the control circuit
  • (d) The overload relay NC contact

Answer: (b) An NO auxiliary contact wired in parallel with the start push button — once the contactor picks up, this contact keeps the coil energised after the button is released.

Q7. Which contact is used for electrical interlocking between two contactors?

  • (a) An NO main contact
  • (b) An NC auxiliary contact of one contactor wired in the other contactor’s coil circuit
  • (c) The coil terminals A1–A2
  • (d) An NO auxiliary contact in series with the overload relay

Answer: (b) An NC auxiliary contact of one contactor wired in the other contactor’s coil circuit — when one contactor is on, its NC contact opens and blocks the other coil.

Q8. Can auxiliary contacts switch a motor directly?

  • (a) Yes, they have the same rating as main contacts
  • (b) No, their current rating is only a few amps for control circuits
  • (c) Yes, if the motor is single-phase
  • (d) No, because they are always NC

Answer: (b) No, their current rating is only a few amps for control circuits — connecting a motor load to them would burn the contacts.

Q9. What does fitting an add-on auxiliary contact block to a contactor do?

  • (a) It increases the main-pole current rating
  • (b) It adds extra NO and NC contacts without changing the main poles
  • (c) It changes the coil voltage
  • (d) It adds overload protection

Answer: (b) It adds extra NO and NC contacts without changing the main poles — the block clips on and is driven by the same armature.

Q10. A contactor is marked “3 NO main + 1 NO + 1 NC auxiliary”. What does this mean?

  • (a) It has 5 main poles
  • (b) It has 3 main NO poles plus one NO and one NC auxiliary contact
  • (c) It has 3 coils and 2 overload relays
  • (d) It can switch 5 motors at once

Answer: (b) It has 3 main NO poles plus one NO and one NC auxiliary contact — the main poles switch the load, the auxiliaries serve the control circuit.

Also read: Breaker Watts Calculator | Breaker and Protection MCQs | All MCQ Topics