Circuit Breaker Types MCQs — Set 8

10 practice questions on breaker sizing and selection — worked load calculations, the 80% rule, and choosing breakers for homes vs industry. Work each one out before checking the answer.

Q1. A 5 kW load runs on 230 V single-phase at 0.9 power factor. What breaker size is needed?

  • (a) 10 A
  • (b) 16 A
  • (c) 32 A
  • (d) 63 A

Answer: (c) 32 A — load current I = 5,000 ÷ (230 × 0.9) = 24.2 A; with a 25% margin, 24.2 × 1.25 = 30.2 A, so the next standard size is 32 A, on 4 mm² cable.

Q2. Under the NEC 80% rule, what is the maximum continuous current on a 20 A breaker?

  • (a) 20 A
  • (b) 16 A
  • (c) 25 A
  • (d) 12 A

Answer: (b) 16 A — a breaker loaded continuously (3 hours or more) must not exceed 80% of its rating: 20 × 0.8 = 16 A.

Q3. Under the NEC 80% rule, what is the maximum continuous load in watts on a 20 A, 120 V circuit?

  • (a) 2,400 W
  • (b) 1,920 W
  • (c) 1,200 W
  • (d) 3,000 W

Answer: (b) 1,920 W — continuous current is 20 × 0.8 = 16 A, so power = 16 × 120 = 1,920 W (the 2,400 W figure is the non-continuous maximum).

Q4. Under the NEC 80% rule, what is the maximum continuous load in watts on a 15 A, 120 V circuit?

  • (a) 1,800 W
  • (b) 1,440 W
  • (c) 900 W
  • (d) 2,400 W

Answer: (b) 1,440 W — continuous current is 15 × 0.8 = 12 A, so power = 12 × 120 = 1,440 W.

Q5. A 7.5 kW load runs on 230 V single-phase at 0.9 power factor. What breaker size is needed?

  • (a) 32 A
  • (b) 40 A
  • (c) 50 A
  • (d) 20 A

Answer: (c) 50 A — load current I = 7,500 ÷ (230 × 0.9) = 36.2 A; with a 25% margin, 36.2 × 1.25 = 45.3 A, so the next standard size is 50 A.

Q6. What is the maximum continuous load in watts on a 30 A, 240 V circuit under the 80% rule?

  • (a) 7,200 W
  • (b) 5,760 W
  • (c) 3,600 W
  • (d) 9,600 W

Answer: (b) 5,760 W — continuous current is 30 × 0.8 = 24 A, so power = 24 × 240 = 5,760 W.

Q7. A 1.5 kW heater runs on 230 V. Which MCB rating suits it?

  • (a) 6 A
  • (b) 10 A
  • (c) 32 A
  • (d) 63 A

Answer: (b) 10 A — load current I = 1,500 ÷ 230 = 6.5 A, so a 10 A MCB covers it with margin, while 6 A would be too small.

Q8. When sizing a breaker, what is the correct relationship between load current, breaker rating and cable capacity?

  • (a) Breaker rating must be at least the load current, and the cable must safely carry at least the breaker rating
  • (b) The breaker rating must be smaller than the load current
  • (c) The cable size does not matter at all
  • (d) The breaker rating must always be double the load current

Answer: (a) Breaker rating must be at least the load current, and the cable must safely carry at least the breaker rating — the breaker protects the cable, so the cable must not be the weakest link.

Q9. Why is a D-curve breaker with a separate overload relay a better choice for a large motor than a plain C-curve MCB?

  • (a) The D curve tolerates the motor’s high starting current, while the overload relay gives proper sustained-overload protection
  • (b) A C-curve MCB cannot be used on motors at all
  • (c) The overload relay increases the motor speed
  • (d) A D-curve breaker needs no cable

Answer: (a) The D curve tolerates the motor’s high starting current, while the overload relay gives proper sustained-overload protection — the two devices together cover starting inrush and running overload.

Q10. A home distribution board and a factory main board need different breakers mainly because:

  • (a) Homes use MCBs and RCCBs at low fault levels, while factories need MCCBs and ACBs at high currents and fault levels
  • (b) Homes need no protection at all
  • (c) Factories use only fuses
  • (d) The voltage in a factory is always 12 V

Answer: (a) Homes use MCBs and RCCBs at low fault levels, while factories need MCCBs and ACBs at high currents and fault levels — the breaker type must match the load size and the available fault current.

Also read: Wire Size Calculator | All MCQ Topics