Circuit Breaker Types MCQs — Set 5
10 practice questions on B, C and D tripping curves — the magnetic trip ranges, with worked numbers. Work each one out before checking the answer.
Q1. What is the magnetic (instantaneous) trip range of a B-curve MCB?
- (a) 1–2 times rated current
- (b) 3–5 times rated current
- (c) 5–10 times rated current
- (d) 10–20 times rated current
Answer: (b) 3–5 times rated current — a B-curve breaker trips magnetically at 3 to 5 times its rated current.
Q2. What is the magnetic trip range of a C-curve MCB?
- (a) 3–5 times rated current
- (b) 5–10 times rated current
- (c) 10–20 times rated current
- (d) 20–30 times rated current
Answer: (b) 5–10 times rated current — a C-curve breaker trips magnetically at 5 to 10 times its rated current.
Q3. What is the magnetic trip range of a D-curve MCB?
- (a) 5–10 times rated current
- (b) 3–5 times rated current
- (c) 10–20 times rated current
- (d) 1–3 times rated current
Answer: (c) 10–20 times rated current — a D-curve breaker tolerates the highest inrush before magnetic tripping.
Q4. A 16 A B-curve MCB trips magnetically at what current range?
- (a) 16–32 A
- (b) 48–80 A
- (c) 80–160 A
- (d) 160–320 A
Answer: (b) 48–80 A — B curve is 3–5× rated current, so 16 × 3 = 48 A and 16 × 5 = 80 A.
Q5. A 20 A C-curve MCB trips magnetically at what current range?
- (a) 60–100 A
- (b) 100–200 A
- (c) 200–400 A
- (d) 20–40 A
Answer: (b) 100–200 A — C curve is 5–10× rated current, so 20 × 5 = 100 A and 20 × 10 = 200 A.
Q6. A 32 A D-curve MCB trips magnetically at what current range?
- (a) 96–160 A
- (b) 160–320 A
- (c) 320–640 A
- (d) 640–1,280 A
Answer: (c) 320–640 A — D curve is 10–20× rated current, so 32 × 10 = 320 A and 32 × 20 = 640 A.
Q7. A 10 A C-curve MCB trips magnetically at what current range?
- (a) 30–50 A
- (b) 50–100 A
- (c) 100–200 A
- (d) 10–20 A
Answer: (b) 50–100 A — C curve is 5–10× rated current, so 10 × 5 = 50 A and 10 × 10 = 100 A.
Q8. Which tripping curve is best for a motor circuit with a high starting (inrush) current?
- (a) B curve
- (b) C curve
- (c) D curve
- (d) A curve
Answer: (c) D curve — its 10–20× magnetic range lets the motor start without nuisance tripping, while still clearing a real short circuit.
Q9. Which tripping curve is normally chosen for domestic lighting and resistive loads with little inrush?
- (a) D curve
- (b) B curve
- (c) C curve for everything
- (d) No curve is needed
Answer: (b) B curve — lighting and resistive loads have almost no inrush, so the sensitive 3–5× B curve gives the fastest short-circuit protection.
Q10. A 63 A C-curve MCB trips magnetically at what current range?
- (a) 189–315 A
- (b) 315–630 A
- (c) 630–1,260 A
- (d) 63–126 A
Answer: (b) 315–630 A — C curve is 5–10× rated current, so 63 × 5 = 315 A and 63 × 10 = 630 A.