Circuit Breaker Types MCQs — Set 2

10 practice questions on MCCBs — moulded case circuit breakers, their ratings, adjustable trips and industrial uses. Work each one out before checking the answer.

Q1. What does MCCB stand for?

  • (a) Miniature Current Control Breaker
  • (b) Moulded Case Circuit Breaker
  • (c) Magnetic Cut-out Circuit Breaker
  • (d) Main Cable Connection Breaker

Answer: (b) Moulded Case Circuit Breaker — the breaker mechanism is housed in a moulded insulating case, unlike the small MCB.

Q2. What is the main difference between an MCCB and an MCB?

  • (a) An MCCB handles much higher currents and usually has adjustable trip settings
  • (b) An MCCB can only be used on DC supplies
  • (c) An MCCB has no thermal trip at all
  • (d) An MCCB cannot be reset after tripping

Answer: (a) An MCCB handles much higher currents and usually has adjustable trip settings — MCCBs commonly cover 100 A to about 2,500 A, while MCBs top out around 125 A.

Q3. Where is an MCCB most commonly used?

  • (a) As the main incomer or distribution breaker in industrial and large commercial boards
  • (b) Inside a mobile phone charger
  • (c) As a lighting switch in a bedroom
  • (d) In place of an earth wire

Answer: (a) As the main incomer or distribution breaker in industrial and large commercial boards — its high rating and breaking capacity suit larger loads.

Q4. What does the adjustable trip setting on an MCCB allow?

  • (a) Changing the supply voltage
  • (b) Setting the overload pickup, for example 0.8 to 1.0 times the rated current
  • (c) Increasing the cable size automatically
  • (d) Testing the earth leakage current

Answer: (b) Setting the overload pickup, for example 0.8 to 1.0 times the rated current — so one MCCB frame can be matched closely to the actual load.

Q5. An MCCB has a frame size of 250 A fitted with a 200 A trip unit. What is the maximum current it will protect at?

  • (a) 250 A
  • (b) 200 A
  • (c) 450 A
  • (d) 50 A

Answer: (b) 200 A — the frame size is the maximum the case can carry, but the trip unit decides the protected current, here 200 A.

Q6. What does “frame size” mean for an MCCB?

  • (a) The physical size of the distribution board
  • (b) The maximum current rating the MCCB frame is built for, within which different trip units can be fitted
  • (c) The length of the cable it protects
  • (d) The number of poles it has

Answer: (b) The maximum current rating the MCCB frame is built for, within which different trip units can be fitted — for example, 160 A, 200 A and 250 A trip units in a 250 A frame.

Q7. A fault level study shows 18 kA at a factory distribution board. An MCB rated 10 kA is not enough. Why is an MCCB a suitable choice here?

  • (a) MCCBs are available with much higher breaking capacities, such as 25 kA and above
  • (b) MCCBs do not need any breaking capacity
  • (c) MCCBs trip only on earth faults
  • (d) MCCBs reduce the fault current to zero

Answer: (a) MCCBs are available with much higher breaking capacities, such as 25 kA and above — the breaker must be able to interrupt the full 18 kA fault safely.

Q8. What is a shunt trip accessory on an MCCB used for?

  • (a) To trip the breaker remotely by an external signal, such as from a fire alarm
  • (b) To increase the rated current
  • (c) To measure the power factor
  • (d) To cool the breaker contacts

Answer: (a) To trip the breaker remotely by an external signal, such as from a fire alarm — energising the shunt trip coil opens the breaker from a distance.

Q9. Which of these is a typical MCCB current range?

  • (a) 1 A to 5 A only
  • (b) 100 A to about 2,500 A
  • (c) 5,000 A to 10,000 A
  • (d) 0.1 A to 0.5 A

Answer: (b) 100 A to about 2,500 A — this range covers distribution and incomer duties that are too large for an MCB.

Q10. Why does an MCCB cost more than an MCB of the same voltage rating?

  • (a) It is larger, handles higher currents, interrupts higher fault levels and offers adjustable protection
  • (b) It contains a built-in transformer
  • (c) It is made of gold contacts only
  • (d) It needs a battery to operate

Answer: (a) It is larger, handles higher currents, interrupts higher fault levels and offers adjustable protection — the heavier contacts, arc chutes and trip unit all add cost.