Charge Controller MCQs — Set 9
10 practice questions on temperature compensation and controller efficiency — why charging voltage must change with temperature. Work each one out before checking the answer.
Q1. What is temperature compensation in a charge controller?
- (a) Cooling the controller with a fan
- (b) Automatically adjusting the charging voltage up or down as the battery temperature changes
- (c) Heating the battery in winter
- (d) Measuring the panel temperature only
Answer: (b) Automatically adjusting the charging voltage up or down as the battery temperature changes — a cold battery needs a higher charging voltage and a hot battery needs a lower one.
Q2. A common temperature compensation rate for lead-acid batteries is:
- (a) −4 mV per °C per cell
- (b) +4 V per °C per cell
- (c) −40 mV per °C per cell
- (d) 0 mV — temperature makes no difference
Answer: (a) −4 mV per °C per cell — the charging voltage falls by about 4 mV per cell for each degree the battery warms above the 25 °C reference.
Q3. A 12 V lead-acid battery (6 cells) has an absorption voltage of 14.4 V at 25 °C. What is the compensated absorption voltage at 0 °C?
- (a) 13.8 V
- (b) 14.4 V
- (c) 15.0 V
- (d) 16.2 V
Answer: (c) 15.0 V — 25 °C colder × 6 cells × 4 mV = 600 mV rise, so 14.4 + 0.6 = 15.0 V.
Q4. The same battery is charged at 35 °C instead of 25 °C. What happens to its absorption voltage?
- (a) It rises to 15.0 V
- (b) It stays at 14.4 V
- (c) It falls to about 14.2 V
- (d) It falls to 12.0 V
Answer: (c) It falls to about 14.2 V — 10 °C warmer × 6 cells × 4 mV = 240 mV lower, so 14.4 − 0.24 ≈ 14.2 V.
Q5. Where should the temperature sensor of a charge controller be placed?
- (a) On the solar panel frame
- (b) On or near the battery, so it measures battery temperature
- (c) On the inverter
- (d) In the shade away from the system
Answer: (b) On or near the battery, so it measures battery temperature — compensation must follow the battery, not the controller or the panels.
Q6. An MPPT controller is 97% efficient. If 300 W comes in from the panels, about how much power reaches the battery?
- (a) 203 W
- (b) 291 W
- (c) 300 W
- (d) 397 W
Answer: (b) 291 W — 300 × 0.97 = 291 W; only about 9 W is lost in the controller.
Q7. What happens to a lead-acid battery charged at full voltage in very hot weather with no temperature compensation?
- (a) It charges perfectly
- (b) It overcharges, loses water and its life is shortened
- (c) It undercharges and freezes
- (d) It produces extra power
Answer: (b) It overcharges, loses water and its life is shortened — in heat the correct charging voltage is lower, so an uncompensated voltage is too high.
Q8. What happens to a lead-acid battery charged in very cold weather with no temperature compensation?
- (a) It overcharges and boils
- (b) It undercharges because the correct cold-weather voltage is higher than the fixed setting
- (c) It charges faster than normal
- (d) Its capacity doubles
Answer: (b) It undercharges because the correct cold-weather voltage is higher than the fixed setting — the battery never reaches full charge and sulphation builds up.
Q9. Why does a charge controller mounted in a hot, unventilated box deliver less charging current?
- (a) The panels produce less current in heat
- (b) The controller derates its output to protect itself from over-temperature
- (c) The battery refuses current when hot
- (d) The load terminals absorb the current
Answer: (b) The controller derates its output to protect itself from over-temperature — good ventilation and shade for the controller keep its full rating available.
Q10. What is the standard reference temperature for battery charging voltages?
- (a) 0 °C
- (b) 10 °C
- (c) 25 °C
- (d) 40 °C
Answer: (c) 25 °C — published charging voltages (e.g. 14.4 V absorption for a 12 V battery) are specified at 25 °C, and compensation adjusts from that point.