Q1. How long does a 100 Ah battery take to charge at 10 A?

  • (a) 10 hours
  • (b) 14 hours
  • (c) 7 hours
  • (d) 20 hours

Answer: (b) 14 hours — time = Ah ÷ A × 1.4 = 100 ÷ 10 × 1.4 = 14 hours from empty.

Q2. How long does a 100 Ah battery take to charge at 20 A?

  • (a) 7 hours
  • (b) 14 hours
  • (c) 3.5 hours
  • (d) 10 hours

Answer: (a) 7 hours — time = 100 ÷ 20 × 1.4 = 5 × 1.4 = 7 hours.

Q3. How long does a 200 Ah battery take to charge at 10 A?

  • (a) 14 hours
  • (b) 28 hours
  • (c) 20 hours
  • (d) 7 hours

Answer: (b) 28 hours — time = 200 ÷ 10 × 1.4 = 20 × 1.4 = 28 hours.

Q4. How long does a 12 Ah battery take to charge at 2 A?

  • (a) 6 hours
  • (b) 8.4 hours
  • (c) 12 hours
  • (d) 4.2 hours

Answer: (b) 8.4 hours — time = 12 ÷ 2 × 1.4 = 6 × 1.4 = 8.4 hours.

Q5. A 100 Ah battery is half discharged (50 Ah used). How long to recharge it at 10 A?

  • (a) 14 hours
  • (b) 7 hours
  • (c) 3.5 hours
  • (d) 10 hours

Answer: (b) 7 hours — only 50 Ah must be replaced: 50 ÷ 10 × 1.4 = 7 hours.

Q6. How much energy does a 200 Ah, 12 V battery store?

  • (a) 1,200 Wh
  • (b) 2,400 Wh
  • (c) 200 Wh
  • (d) 16.7 Wh

Answer: (b) 2,400 Wh — energy = Ah × V = 200 × 12 = 2,400 Wh (2.4 kWh).

Q7. A load needs 800 W. Allowing 25% margin, what size inverter should you choose?

  • (a) 800 VA
  • (b) 1,000 VA
  • (c) 600 VA
  • (d) 1,600 VA

Answer: (b) 1,000 VA — 800 × 1.25 = 1,000 VA; the inverter must be bigger than the load it supplies.

Q8. A UPS has a 100 Ah, 12 V battery and powers a 400 W load. Roughly how long is the backup?

  • (a) 3 hours
  • (b) 6 hours
  • (c) 1.5 hours
  • (d) 12 hours

Answer: (a) 3 hours — stored energy = 100 × 12 = 1,200 Wh, so backup = 1,200 ÷ 400 = 3 hours (ideal; real backup is a little less).

Q9. A 100 Ah lithium battery charges at 20 A. Roughly how long does it take from empty?

  • (a) 5.5 hours
  • (b) 7 hours
  • (c) 14 hours
  • (d) 10 hours

Answer: (a) 5.5 hours — lithium is about 95% efficient, so its factor is about 1.1: 100 ÷ 20 × 1.1 = 5.5 hours.

Q10. What size charger is right for a 100 Ah lead-acid battery?

  • (a) 10–20 A
  • (b) 1–2 A
  • (c) 50 A
  • (d) 100 A

Answer: (a) 10–20 A — a charger should be about 10–20% of the battery’s Ah rating; below 10% it takes over a day, above 20% a lead-acid battery overheats.