Cable Types MCQs — Set 7

10 questions on choosing the right cable size for a load — design current, the 25% margin and the watts a cable wastes as heat.

Q1. A 5 kW load at 230 V with power factor 0.9 draws 24.2 A, and with a 25% margin the design current is 30.2 A. Which cable size is needed?

  • (a) 1.5 mm²
  • (b) 2.5 mm²
  • (c) 4 mm²
  • (d) 10 mm²

Answer: (c) 4 mm² — I = 5,000 ÷ (230 × 0.9) = 24.2 A, × 1.25 = 30.2 A, which needs the 4 mm² rating (about 32 A clipped direct).

Q2. A 3 kW resistive heater at 230 V draws 13.0 A, and with a 25% margin the design current is 16.3 A. Which cable size is needed?

  • (a) 1.5 mm²
  • (b) 2.5 mm²
  • (c) 6 mm²
  • (d) 10 mm²

Answer: (b) 2.5 mm² — I = 3,000 ÷ 230 = 13.0 A, × 1.25 = 16.3 A, which fits the 2.5 mm² rating of about 23 A clipped direct.

Q3. A 2 kW heater at 230 V draws 8.7 A. Which cable size is enough?

  • (a) 1.5 mm²
  • (b) 10 mm²
  • (c) 16 mm²
  • (d) 25 mm²

Answer: (a) 1.5 mm² — I = 2,000 ÷ 230 = 8.7 A, well within the 1.5 mm² rating of about 16 A clipped direct.

Q4. A 4 kW load at 230 V with power factor 0.9 draws 19.3 A, and with a 25% margin the design current is 24.2 A. Which cable size is needed?

  • (a) 1.5 mm²
  • (b) 2.5 mm²
  • (c) 4 mm²
  • (d) 6 mm²

Answer: (c) 4 mm² — I = 4,000 ÷ (230 × 0.9) = 19.3 A, × 1.25 = 24.2 A, which needs the 4 mm² rating of about 32 A clipped direct.

Q5. A 1.5 kW motor at 230 V with power factor 0.8 draws 8.2 A, and with a 25% margin the design current is 10.2 A. Which cable size is enough?

  • (a) 1.5 mm²
  • (b) 4 mm²
  • (c) 6 mm²
  • (d) 10 mm²

Answer: (a) 1.5 mm² — I = 1,500 ÷ (230 × 0.8) = 8.2 A, × 1.25 = 10.2 A, within the 1.5 mm² rating of about 16 A clipped direct.

Q6. How much power is wasted as heat in a 25 m run of 2.5 mm² cable carrying 20 A, if the loop resistance is 0.371 Ω?

  • (a) 37 W
  • (b) 74 W
  • (c) 148 W
  • (d) 296 W

Answer: (c) 148 W — P = I²R = 20² × 0.371 = 400 × 0.371 = 148 W lost as heat in the cable.

Q7. How much power is wasted as heat in a 30 m run of 1.5 mm² cable carrying 10 A, if the loop resistance is 0.726 Ω?

  • (a) 7.3 W
  • (b) 36 W
  • (c) 73 W
  • (d) 145 W

Answer: (c) 73 W — P = I²R = 10² × 0.726 = 100 × 0.726 = 72.6 W, about 73 W.

Q8. How much power is wasted as heat in a 20 m run of 4 mm² cable carrying 30 A, if the loop resistance is 0.184 Ω?

  • (a) 55 W
  • (b) 110 W
  • (c) 166 W
  • (d) 332 W

Answer: (c) 166 W — P = I²R = 30² × 0.184 = 900 × 0.184 = 166 W lost as heat in the cable.

Q9. What is the resistance of 100 m of 2.5 mm² copper cable, given 7.41 Ω/km?

  • (a) 0.074 Ω
  • (b) 0.74 Ω
  • (c) 7.41 Ω
  • (d) 74.1 Ω

Answer: (b) 0.74 Ω — 100 m is 0.1 km, so R = 7.41 × 0.1 = 0.741 Ω, about 0.74 Ω.

Q10. What is the resistance of 50 m of 4 mm² copper cable, given 4.61 Ω/km?

  • (a) 0.023 Ω
  • (b) 0.23 Ω
  • (c) 2.31 Ω
  • (d) 4.61 Ω

Answer: (b) 0.23 Ω — 50 m is 0.05 km, so R = 4.61 × 0.05 = 0.231 Ω, about 0.23 Ω.

Also read: Cable Sizing MCQs | All MCQ Topics