Cable Joint MCQs — Set 8
10 practice questions on crimping and cable lugs — the compression connection at the heart of most joints — with answers and explanations.
Q1. What does crimping do in a cable joint?
- (a) It melts the conductor with a flame
- (b) It cuts the conductor to length
- (c) It compresses a metal connector or lug onto the conductor with a die
- (d) It glues the conductor to the insulation
Answer: (c) It compresses a metal connector or lug onto the conductor with a die — the die squeezes the connector tightly around the conductor strands.
Q2. How is the correct compression force set when crimping?
- (a) By the tool die size matched to the lug and conductor
- (b) By guessing how hard to squeeze
- (c) By heating the lug first
- (d) By the colour of the cable sheath
Answer: (a) By the tool die size matched to the lug and conductor — the die size fixes the amount of compression, so the right die for the lug size must be used.
Q3. What happens if the crimping die is too small for the lug?
- (a) The lug becomes looser
- (b) The conductor strands are over-compressed and damaged
- (c) The insulation becomes stronger
- (d) The crimp is perfect
Answer: (b) The conductor strands are over-compressed and damaged — too much compression crushes and breaks strands, weakening the conductor.
Q4. What happens if the crimping die is too large for the lug?
- (a) The crimp is loose, giving a high-resistance connection that overheats
- (b) The lug melts
- (c) The joint becomes stronger
- (d) The conductor strands are cut cleanly
Answer: (a) The crimp is loose, giving a high-resistance connection that overheats — an under-compressed crimp does not grip the conductor, so it heats up under load.
Q5. When is a hydraulic crimper used instead of a hand crimper?
- (a) For cutting cables
- (b) For stripping insulation
- (c) For very small wires only
- (d) For large conductors, where hand force is not enough
Answer: (d) For large conductors, where hand force is not enough — hydraulic tools give the high force needed to crimp big lugs properly.
Q6. How is a completed crimp checked?
- (a) By painting it
- (b) By weighing it
- (c) By visual inspection and a pull test — the lug must not move on the conductor
- (d) By leaving it in water
Answer: (c) By visual inspection and a pull test — the lug must not move on the conductor — a good crimp is neat, fully compressed, and holds firmly when pulled.
Q7. Which lug material should be used on a copper cable conductor?
- (a) A plastic lug
- (b) An aluminium lug
- (c) A steel lug
- (d) A copper lug
Answer: (d) A copper lug — matching metals avoids corrosion at the connection; copper on copper is the correct pairing.
Q8. When is a bi-metallic lug used?
- (a) When no crimping tool is available
- (b) When joining a copper conductor to an aluminium conductor or terminal
- (c) When joining two copper conductors
- (d) When the cable is very short
Answer: (b) When joining a copper conductor to an aluminium conductor or terminal — the bi-metallic lug has a copper palm and an aluminium barrel, one for each metal.
Q9. Why is a bi-metallic lug needed for a copper-to-aluminium connection?
- (a) To increase the voltage
- (b) To change the cable colour
- (c) To prevent galvanic corrosion between the two different metals
- (d) To make the joint heavier
Answer: (c) To prevent galvanic corrosion between the two different metals — copper and aluminium in direct contact corrode, but the bi-metallic lug keeps them apart.
Q10. Before crimping, the conductor must be:
- (a) Left fully insulated
- (b) Bent sharply back on itself
- (c) Coated in water
- (d) Stripped of insulation and clean, with no dirt or oxide on the strands
Answer: (d) Stripped of insulation and clean, with no dirt or oxide on the strands — a clean conductor is essential for a low-resistance crimp.
Also read: Batten Wiring System | All MCQ Topics